8-4
Operating and Maintenance Manual
Diagnostics
code 504275001 Rev. September 2010
SIGNALLING EVENTS
Message
Meaning
SHUTTING DOWN DUE TO END OF
AUTONOMY
UPS shut down due to the end of autonomy.
SHUTTING DOWN DUE TO INCOR-
RECT THREE-PHASE SEQUENCE
UPS shut down due to an incorrect three-phase sequence in input.
START-UP WITH BATTERY FAILED
Start-up with battery failed.
BATT.CAL.INTERRUPTED
Battery calibration interrupted.
MAXIMUM TIME ON BATTERY
Maximum time on battery.
MAXIMUM TIME ON RESERVE
Maximum time on autonomy reserve.
START-UP ERROR
Error in starting up.
START-UP AUTHORISED WHEN
THERE ARE ONGOING ALARMS
UPS start-up authorised in the presence of alarms.
STARTUP AUTHORISED WITH A
NEW CONFIG.
UPS start-up authorised with a new con
fi
guration.
SHUTTING DOWN DUE TO INCOR-
RECT CONFIGURATION
UPS shutting down due to an incorrect con
fi
guration.
POWER MODULE FW UPDATE
The Power Module Firmware updated.
INFORMATION EVENTS
Message
Meaning
STARTUP BY USER N
UPS start-up by user.
SHUTTING DOWN BY USER
UPS shut down by user.
AUTOMATIC STARTUP:
Automatic UPS start-up.
DELAYED SHUTTING DOWN
The UPS was shut down by programming a delayed shutdown.
BATTERY CHARGER START IN
STAND-BY
The battery charger started in standby.
UPS ON BATTERY
UPS on battery.
UPS ON MAINS
UPS on mains.
OUTPUT OFF
The output is off
BATTERY TEST \NEXECUTED
Batteries tested.
BATTERIES CALIBRATED
Batteries calibrated.
ALARMS
Message
Meaning
INVERTER FAILURE
Failure occurred in the Inverter circuit.
BOOSTER FAILURE
Failure occurred in the Booster circuit.
BATTERY CHARGER FAILURE
Failure occurred in the Battery Charger circuit.
OVERHEATING
Overheating. Check the UPS ventilation system.
OVERLOAD
Overload. Check the load level connected to the UPS.
HVBUS RUNAWAY
Anomalous high voltage on the DC BUS.
EXC. IN OUT DC LEVEL
Excessive DC voltage in output.
EXCESS.BATTERY V
Battery voltage too high.
MODULE COMMUNICATION FAILED Failure of the communication system with the Power Modules.
LOAD NOT PROTECTED
Load not protected by the UPS
LAST LINE ON THE MAIN ‘BATTERY’ FRAME
Message
Meaning
BATTERIES ON STAND-BY
Batteries on stand-by.
RUNNING DOWN
Batteries running down.
AUTONOMY RESERVE
Autonomy reserve.
END OF AUTONOMY
End of autonomy, UPS shutting down.
CHARGING – F1
Battery recharging status: Phase 1
CHARGING – F2
Battery recharging status: Phase 2
CHARGING – MAINT.
Recharging batteries in maintenance.
BATTERIES BEING TESTED
Batteries being tested.
BATTERY EQUALIS.
Batteries being equalised.
BATTERIES FAILED
Batteries failed.