7-4
Operating and Maintenance Manual
Control panel
code 504275001 Rev. September 2010
Note:
press ‘ENTER’ to change the X value and consequently vary the phase of which you are reading
the data
Measurements
Input X
Power
Power absorbed by the UPS by the mains on phase X [W]
Appar. Power
Apparent power absorbed by the UPS by the mains on pha-
se X [VA]
Vrms
Effective voltage in input to the UPS on phase X [V RMS]
Linked Vrms
Effective line voltage between the phases in input to the UPS
[V RMS]
Bypass Vrms
Effective voltage in input to the UPS on phase X, for the bypass
line [V RMS]
Irms
Effective current absorbed by the UPS by the mains on phase X
[A RMS]
Peak I Value
Peak current absorbed by the UPS by the mains on phase X [A]
Frequency
Frequency of the voltage sinusoid in input to the UPS on phase X
[Hz]
Peak I Factor
Peak factor applied by the UPS to the mains on phase X
Power Factor
Power factor applied by the UPS to the mains on phase X
Note:
press ‘ENTER’ to change the X value and consequently vary the phase of which you are reading the
data
Measurements
Batteries
Voltage
Voltage measured at the ends of the batteries [V]
Current
Current supplied by the batteries (negative if the batteries are
being charged) [A]
Residual Ca-
pac.
Battery charged status, expressed as a percentage [0-100%]
Chg Status
Working status of the battery charger
Tot autonomy
Total autonomy the UPS would have with batteries charged
100%
Res. autonomy
Residual autonomy of the UPS
End of aut V
Battery threshold voltage for end of autonomy
No. run downs
Total number of times the batteries have been completely run
down
Use
Total number of hours the UPS has been running on battery
Cal.
Day and time the last calibration was made
No. Calibrations Total number of calibrations made
Measurements
Misc.
Internal Temp.
Temperature inside the UPS [°C]
H.V. Bus pos.
Voltage on the DC BUS positive [V]
H.V. Bus neg.
Voltage on the DC BUS negative [V]
Alarms
Alarms Log. See chapter 8.
Historical Data
UPS operation
Total time the UPS has been working
With battery
Total time the UPS has been running on battery
Battery charger Op.
Total time the battery charger has been working
Tot. run downs
Total number of times the batteries have been completely run down
Booster Int.
Total number of Booster interventions
Bypass Int.
Total number of Bypass interventions
Batt. Calibr.
Total number of battery Calibrations
Battery ch.Cycles
Total number of battery charger cycles
Batt.eq.cycles
Total number of battery equalisation cycles