2-6
Operating and Maintenance Manual
Technological
Description
code 504275001 Rev. September 2010
2.4 TECHNICAL
SPECIFICATIONS
Input nominal voltage:
V = 400
(Tri + N)
+ 15% - 20%
(Only Archimod 20/40KVA V = 230 V +15% -20% with single input)
Input frequency:
Hz = 50 / 60 +/- 2%
Input connections:
Tri + Neutral
THD input current:
< 3%
Input power factor:
> 0.99
OUTPUT CHARACTERISTICS
Maximum
current (tri/tri):
28,99 A
57,98 A
86,97 A
115,96 A
144,95 A
173,94 A
Maximum
current
(tri/single):
86,96 A
-
-
-
-
-
Maximum
current
(single/tri):
28,99 A
-
-
-
-
-
Maximum
current
(single/single):
86,96 A
-
-
-
-
-
Output nominal voltage:
V = 400 +/- 1%
(Only Archimod 20/40KVA V = 230 V ± 1% with single output)
Output nominal frequency:
Hz = 50/60 sincronized
Output connections:
T Neutro
Efficiency:
- Mains (On Line)
- Mains (Eco mode)
95%
99%
Over load:
125% for 10 min - 150% for 1 min
Factor crest
3,5:1
GENERAL CHARATERISTICS
Rated Power:
20 KVA
40 KVA
60 KVA
80 KVA
100 KVA
120 KVA
Active Power:
16 KW
32 KW
48 KW
64 KW
80 KW
96 KW
Technology:
On Line, double conversion VFI – SS - 111
Configuration I/O:
Triphase / Triphase
(OnlyArchimod 20/40KVAcan be configuredsingle/single, single/tri, tri/single, tri/tri by user)
UPS architecture:
Modular with 6,7 KVA power modules (cos
Ê
0,8).
Housed in a single cabinet. Expendable, redundant N+X
(except for Archimod 120KVA).
INPUT CHARACTERISTICS
Maximum current
(tri/tri):
37 A
74 A
111 A
148 A
185 A
222 A
Maximum current
(tri/single):
37 A
-
-
-
-
-
Maximum current
(single/tri):
111 A
-
-
-
-
-
Maximum current
(single/single):
111 A
-
-
-
-
-
Summary of Contents for ARCHIMOD 100