8-2
Operating and Maintenance Manual
Diagnostics
code 504275001 Rev. September 2010
8.2 MESSAGES
In this paragraph the messages that appear on the unit’s display are listed, also giving the most
likely cause that could have generated them.
If you are unable to solve the problem then please contact the Technical Service.
FIRST LINE OF THE MAIN FRAME
Message
Meaning
SERVICE MODE
UPS in the Service Mode.
All settings via the display, maintenance functions and updates are possible.
UPS START-UP
UPS starting up. The UPS control system checks the correct con
fi
guration status
before entering the ‘Normal’ or ‘Service’ operating mode.
The UPS is in Bypass during this initialisation phase.
UPS IN BYPASS
UPS in Bypass. The load is not protected by the UPS in this con
fi
guration.
FORCED BYPASS
The UPS has entered the forced Bypass mode via con
fi
guration on the display.
BYPASS INPUT KO
Bypass input KO; some problems have arisen on the Bypass line.
It is not possible to feed the loads directly off the mains.
‘OUTPUT OFF’
Output off. Con
fi
guration obtained via the display or subsequent to a UPS malfunc-
tion.
UPS ON BATTERY
UPS on battery. The cause for this con
fi
guration is a failure in the UPS feeding
system.
BATTERY CALIBRATION
The UPS is calibrating the batteries.
BATTERY TEST
The UPS is testing the batteries to check their status and that they are working
properly.
BATTERY EQUALIS.
The UPS is equalising the batteries.
BUZZER OFF
The buzzer is turned off.
AUTONOMY RESERVE!
Battery charge level is at minimum.
MODULE FAILED
One or more Power Modules have failed. They must either be repaired or changed.
BATTERIES KO
Batteries failed. Check their operation and replace them if necessary.
OVERLOAD
The total load is higher than the UPS’s rated power.
Switching to Bypass.
OVERHEATING
The temperature inside the UPS is outside the nominal range.
DC OUT LEVEL FAILURE
A failure of the UPS has caused a DC voltage in output.
HVBUS RUNAWAY FAILURE
A failure of the UPS has caused a voltage level on the High Voltage Bus out of con-
trol.
RUNAWAY BATTERIES
Battery voltage out of control.
Either the batteries or battery charger are/is malfunctioning.
3V battery
fl
at
The control board’s 3V battery is
fl
at.
Shutdown in progress
The UPS is shutting down.
Batteries being Charged
The UPS is charging the batteries.
<ESC> to interr.
By pressing ESC key the function requested is cancelled.
UPS IN EMERGENCY!
UPS in Emergency.
UPS OFF!
UPS off.
UPS STOPPED!
The UPS has stopped.
NO MAINS
No mains.
VERY HIGH MAINS
The mains voltage is very high but still inside the range allowed.
MAINS OFF TOLL.
Mains voltage is out of the range allowed.
The UPS switches to battery and Bypass is disabled.
MAINS NOT SYNC.
Mains not synchronised; Bypass disabled.
INCORRECT SEQUENCE
Invalid input sequence, check correct supply connection.