4-2
Operating and Maintenance Manual
Unpacking
code 504275001 Rev. September 2010
UPS
Minimum clearances recommended for the UPS
X=100 mm / Y=200 mm
UPS
Battery
Cabinet
Minimum clearances recommended for the UPS ARCHIMOD
®
+ ARCHIMOD
®
BATTERY
X=100 mm / Y=200 mm
To better protect the batteries bear in mind that the average life of the batteries is strongly
influenced by the environmental operating temperature.
Place the unit on premises where the temperature ranges b18°C (64.4°F) and +23°C
(73.4°F) which will guarantee a very long battery life.
Before commencing installation, make sure there is enough lighting on the equipment so that
each single detail can be seen easily.
Use artificial lighting if natural lighting is not enough for the aforementioned requirements.
If maintenance work has to be done on parts that are insufficiently illuminated, it is compulsory
to use portable lighting, being careful not to create shadows that will prevent or reduce visibility
on the point you are working on or on the surrounding areas.
4.3 POSITIONING AND UNPACKING
To position and unpack the UPS please follow this procedure:
1. Take the UPS to the place of installation with a forklift truck and/or a transpallet of a suitable
capacity and type;
2. Remove the film and cardboard protecting the UPS;
3. Lower the 4 adjustable feet under the UPS base until the 2 side L-shaped supports are slightly
raised, including the wood fixed to them;
4. Remove the 2 side L-shaped supports by undoing the 4 screws on each side securing it to
the UPS base;
5. If it is necessary moving the UPS to position it better, lift the 4 feet until the UPS is resting
on the wheels;
6. Check perpendicularity and level of the UPS with the floor with a suitable instrument (by
adjusting the feet): Please note: lock the 4 feet with the check nut;
7. Mount the 2 side base strips with the screws supplied.
Check that the UPS ARCHIMOD
®
technical data on the plate on the sticker affixed on the inside
panel of the door, inside the hatch of the UPS, correspond to the material bought, described
on the delivery document.