Forcing a Parameter Reset
It is possible to invoke the Parameters Crash Screen at controller boot by the upper left
and right touch-pads on the screen during the boot-count-down.
Ram Reset Touch-pads
You can then reset all parameters to factory default. If you see a fatal error crash screen
before the count-down starts, press and hold the touch-pads, and then turn the controller
power on. The boot sequence will then go directly to the crash screen.
DIAGNOSTIC MENUS
Pushing the
Diag Menu
button in the Action menu takes you to the Diagnostics Menu.
Diagnostic Menu
It is usable for troubleshooting. It is not necessary to access these menus under normal
operating conditions.
HPAD Diagnostics
HPAD stands for “High Performance Analog to Digital converter”. It is the board in the
MC³ that takes the Load Cell signal as input and produces a digital value (Counts) as
output. This screen helps you diagnose weight indication related problems.
HPAD Diagnostics
Counts:
HPAD output counts. With default HPAD scaling settings, 0 –
1,000,000 corresponds to 0 – 3 mV/V relative output of the load cell.
A value below 255 will turn on the
LoadCell Underl
logical output. A
value above 1048320 will turn on the
LoadCell Overl
logical output.
35.00.EX O&M Manual
56