Select Column
This button switches the active scroll area between the Physical and
Logical columns. First select the physical output you want to work
with, using the Up and Down arrow buttons. Then push the
Select
Column
button to map it to a physical output, again using the Up and
Down arrow buttons.
Invert Off/On
This button inverts the logic of the physical output. For example, if
Rack 1 Output 1
is mapped to the logical output
Fault
, you would
typically invert that output, so that the output contact is closed when
there is no fault. An inverted output will have a
1
in the
IV
column.
The button is only available when you have the Physical Output
selected, since the Invert property is associated with the physical
output.
Force None/Off/On
This button toggles the
FC
indication through Forced On
1
, Forced
Off
0
or no Force
-
. There will be a blinking indication on the Main
Screen if forces are present. The button is only available when you
have the Physical Output selected, since the Force property is
associated with the physical output.
Alarming
Since un-mapped logical outputs are not visible in this screen, this
button takes you to another screen where you can set the Faults and
Warnings properties for all logical outputs, both mapped and un-
mapped.
WARNING:
If you have made changes to the mapping, press
Accept
before pressing
Alarming
. If
you don’t, the mapping changes will be lost.
Set the Warning and Fault properties for all Logical Outputs by
scrolling to the output with the up and down arrows and then push the
Select F/W
button. When you are done, push the
Return
button.
Accept
When you are done with your Logical Outputs configuration, push this
button to make your configuration changes permanent. The button is
only available when you have the
Logical Output
column selected.
Esc
Takes you back to the Inputs and Outputs Setup Screen. If you push
this button without first pushing the
Accept
button, The Digital
Outputs configuration will be restored to the condition it had when you
entered this menu.
Logical Outputs
Logical Output
Description
35.00.EX O&M Manual
39