
85-03-00944
18 |
P a g e
FINISHING MATERIALS INSTALLATION
All finishing materials that surround this fireplace’s arch profile must extend out from the face surface of this fireplace 1
inch.
Tiles and Faux Rock
If installing Tiles or Faux Rock, first install a ½” thick (minimum) Cement Board (Hardibacker or Durock Brand) over the
face of the fireplace and framing members. Follow by applying Thinset mortar (no polymer additives) using ¼” square
notched trowel on the cement board surface. Finally, install tile to reach a finish material depth of 1 inch.
Marble and Granite Slabs
If installing Marble or Granite slabs as fascia materials, specify that the inner edges that will be adjacent to the Glass Door
are polished. Rough Framing should be created at 19” depth with the front surface of this fireplace protruding out ½” from
the framing surface.
NOTE: On the left side of this unit, rotate the 2x4 stud so the 1-1/2” thickness is towards the
control module box.
Install 1/2'” thick drywall on framing members so that its outer surface is flush with the front face of
this fireplace. Attach Marble or Granite slabs to face of unit and to drywall surface using adhesive that does not offgas
when hot.
In the area defined as “NONCOMBUSTIBLE ZONE” [FIGURE 7], only NONCOMBUSTIBLE MATERIALS ARE
ALLOWED.
When this fireplace is installed in a framed cavity that is 19-1/2” deep, the facing material finishing guide will pro-
trude out into the room 1 inch. Build finishing materials to 1 inch thickness and use the built-in guides for edge
alignment of fascia material. Consult section “FRAMING DEPTH and FINISHING GUIDES”.
WARNING:
The cross hatched areas labeled as “NONCOMBUSTIBLE ZONE” must be covered with noncombustible finishing
materials that is 1-inch thick, minimum. DO NOT ALLOW COMBUSTIBLE FACING MATERIALS TO ENCROACH IN THIS
AREA! Conforming combustible mantels may be installed on top of the non-combustible facing in the top noncombustible zone.
NON-COMBUSTIBLE ZONE
(ALL HATCHED AREAS)
FINISHING GUIDES
A
Summary of Contents for FV41-ARCH
Page 32: ...85 03 00944 32 P a g e 45 1 2 42 1 2 46...
Page 34: ...85 03 00944 34 P a g e...
Page 36: ...85 03 00944 36 P a g e FEET MAXIMUM...
Page 59: ...85 03 00944 59 P a g e...
Page 60: ...85 03 00944 60 P a g e...
Page 61: ...85 03 00944 61 P a g e...
Page 62: ...85 03 00944 62 P a g e...
Page 63: ...85 03 00944 63 P a g e...
Page 64: ...85 03 00944 64 P a g e...
Page 65: ...85 03 00944 65 P a g e...