Installation manual
M-WRG-II M-U
2
- 49 -
Meltem Wärmerückgewinnung GmbH & Co. KG
Am Hartholz 4 · D-82239 Alling
[email protected] · www.meltem.com
VENTILATION THE RIGHT WAY
V E N T I L A T I O N & H E A T R E C O V E R Y
9.9
Inserting flat ductwork into channels
NOTICE
If you are using flexible pipes, continue from section “8.11 Cutting flexible pipes to
► Insert a fitting, e.g. the flat
ductwork connector M-WRG-FK-V,
part no. 5591 (item 1 in Fig. 27), into
the opening in the wall box.
NOTICE
All fittings (flat ductwork connectors,
bends, angles, etc.) inserted into the
opening in the wall box must have the
external dimensions 115 x 58 mm.
Elements with the external dimen-
sions 110 x 54 mm, e.g. flat ductwork,
are designed to be inserted into the
fittings. They must not be inserted
directly into the opening in the wall
box.
► Join individual elements of the flat ductwork to create partial sections and seal every
join with a layer of sealing tape 30 mm wide.
► Insert the first section of the flat ductwork into the fitting, e.g. the flat ductwork
connector M-WRG-FK-V, part no. 5591, on the wall box and seal the join with sealing
tape (item 2 in Fig. 27).
► Insert the sections of flat ductwork into the channel one after another and seal every
join with sealing tape.
► Fill the gaps around the flat ductwork with insulating material or other suitable filling
materials. This will improve both the seal and the insulation.
Fig. 55: Fixing ductwork connections with sealing tape
1
2