Installation manual
M-WRG-II M-U
2
- 12 -
Meltem Wärmerückgewinnung GmbH & Co. KG
Am Hartholz 4 · D-82239 Alling
[email protected] · www.meltem.com
VENTILATION THE RIGHT WAY
V E N T I L A T I O N & H E A T R E C O V E R Y
— The lateral distance between two wall boxes must not be less than 200 mm to
prevent an air short circuit between the ventilation units.
Fig. 5: Lateral minimum distance between two wall boxes, dimensions in millimetres
min. 200
Dividing wall
NOTICE
Follow the notes in Table 2 on page 26 when planning the unit. This contains informa-
tion about the types of mains and control cable for each ventilation unit and the recom-
mended operating options.
3.2
Unrestricted access to the ventilation unit
The ventilation unit must always be freely accessible for operation and maintenance.
►
Make sure that the ventilation unit is not covered or obstructed when the room is
subsequently decorated and furnished, otherwise it cannot be operated and it will not
be possible to replace the air filters. You should therefore maintain a clearance of at
least 15 cm in front of the ventilation unit cover.
►
Make sure that the supply and extract air openings are not covered when the room is
subsequently decorated and furnished, otherwise the ventilation unit’s functions may
be impaired.
3.3
Additional planning notes for this installation kit
3.3.1
Fire safety and soundproofing
WARNING
Observe the relevant fire safety and soundproofing regulations
► Observe the regulations concerning the fire behaviour of building materials and
components as defined in DIN 4102 (EN 13501).
► Observe the regulations concerning soundproofing in buildings as defined in
DIN 4109, particularly the requirements for insulation against airborne and impact
sound.
►
Observe the building regulations applicable in your country.