Installation manual
M-WRG-II M-U
2
- 13 -
Meltem Wärmerückgewinnung GmbH & Co. KG
Am Hartholz 4 · D-82239 Alling
[email protected] · www.meltem.com
VENTILATION THE RIGHT WAY
V E N T I L A T I O N & H E A T R E C O V E R Y
3.3.2 Flat ductwork
NOTICE
► Observe the following recommendations when using flat ductwork to avoid unneces
-
sary pressure losses in the ducts.
—
Make sure that the wall aperture does not affect the local static loading and ther
-
mal insulation requirements.
— Horizontal runs in the external wall should be as short as possible.
—
The total length of a flat duct should not exceed 6 m, as permitted by the static
calculations.
—
Minimise the number of bends in the flat ductwork.
3.3.3 Flexible pipes
NOTICE
► Observe the following recommendations when using flexible pipes to avoid unnec
-
essary pressure losses in the pipes.
—
Always connect two flexible pipes to the flexible pipe connection.
—
As far as possible, use flexible pipes with a diameter of 75 mm.
—
The total length of each flexible pipe should not exceed 10 m.
—
Minimise the number of bends in the flexible pipes.
—
Run the two flexible pipes of a flexible pipe connection in parallel to one another.
The minimum distance between the flexible pipes must not be less than 3x the
pipe diameter.
3.4
Retrospectively flush-mounting the installation kit
WARNING
Danger from emerging gas or electric shock
► Make sure that there are no supply lines in the vicinity of the wall breakthrough (e.g.
power, gas or water).
► Make sure that the wall breakthrough does not affect the local static loading require
-
ments.
►
Fit a lintel if necessary.
► If you are installing the kit retrospectively, run the flexible pipes in a suspended
ceiling.