9.4.2 External control input
With the external control input supplied as standard,
the M-WRG-II unit has an additional input terminal for
230 V AC (working voltage range: 85 V AC to 265 V AC /
50-60 Hz) to which a switch, time switch, motion detector
or similar may be connected.
The external control input is equipped with a time-delay
relay that can be used to set a switch-on delay and a
run-on time:
— Switch-on delay: the M-WRG-II unit does not start until
the set time has elapsed.
— Run-on time: the M-WRG-II unit does not switch to the
previously active ventilation program until the set time
has elapsed.
In addition, the following options are available for the
external control input supplied as standard:
—
M-WRG-II O/EST-1 (without switch-on delay, part no. 721005)
—
M-WRG-II O/EST-2 (without run-on time, part no. 721006)
Windowless rooms can be ventilated in accordance with DIN 18017-3 in combination with
the M-WRG-II O/NOF option (part no. 721004).
Fig. 47: Connection diagram for
external control input
L
230 V~
N
S L N M-WRG-II
Mains cable type:
NYM-J 4 x 1.5 mm
2