DIP switch settings
1 or 2 Fan speeds
Use DIP Switch S1.5 to select between 1 and 2 fan speeds configurations as follows:
1 Fan speed:
S1.5 – OFF
2 Fan speeds:
S1.5 – ON
Tel: +972-3-9626462
Fax: +972-3-9626620
support@meitavtec.com
ETN24-PM-HP-SUPER-BL
Owner’s manual & Technician Settings
Pg. 4
Internal/External sensor
Use DIP Switches S1.1, S1.2 and S1.3 to select between Internal (default) and External
sensor configuration as follows:
Internal sensor: S1.1, S1.3 – ON,
S1.2 – OFF
External sensor: S1.1, S1.3 – OFF, S1.2 – ON
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
2 Fan speeds
1 Fan speed
ON
1 2 3 4 5 6
Internal
sensor
External
sensor
ON
1 2 3 4 5 6
Compressor delay
Use DIP Switch S1.4 to activate the 3 minutes compressor delay as follows:
Enable compressor delay: S1.4 – OFF
Disable compressor delay: S1.4 – ON
Note: During delay, the temperature scale symbol (°C/°F) will flash.
ON
1 2 3 4 5 6
Enable
delay
Disable
delay
ON
1 2 3 4 5 6
Heat pump configuration
Use DIP Switch S1.6 to select between heat pump configuration as follows:
Active in heat:
S1.6 – OFF
Active in cool:
S1.6 – ON
ON
1 2 3 4 5 6
Heat pump
Active in heat
Heat pump
Active in cool
ON
1 2 3 4 5 6