APPLICATION

T8621A,C,D, CHRONOTHERM III

FUEL SAVER THERMOSTATS

These thermostats provide energy saving control for a

24 Vac heating/cooling system as indicated in Table 1, and
are powered direct from the control transformer.

As long as thermostat is continuously powered, the

thermostat will be compatible with any control system.

These models include a SYSTEM LED, which is on

when the thermostat is signaling for heating or cooling. Heat
and cool anticipation is fixed in all models; no adjustment is

necessary. Cycle rates are adjustable for highest stage of
heating.

Fan operation option switch is included on SUPER

TRADELINE model to select fan operation for electric heat
application.

12/24 hour clock conversion and 

°

C/

°

F conversion is

available on some models only.

C. H.

Form Number 69-0330—3

Rev. 12-90

©Honeywell Inc. 1990

INSTALLATION

IF NEW INSTALLATION

Run cable to a hole at the selected wall location, and pull

about 3 in. [76 mm] of wire through the opening. Color-
coded, 18 gauge thermostat cable with one conductor for
each wiring terminal is recommended. Good service prac-
tice recommends selecting cable with one or two more
conductors than the immediate application requires.

MOUNTING SUBBASE

IMPORTANT

The T8621 requires an additional conductor to
transformer common to provide continuous 24 V
power for thermostat operation.

Set the system switch in the OFF position before
mounting the subbase.

The subbase does not require leveling for proper opera-

tion, but for appearance only.

Remove thermostat from subbase (Fig. 1).
The subbase mounts directly onto the wall with the

screws and anchors included in the package. If drywall
construction, plastic anchors must be used; use the sub-
base as a template, and with a pencil, mark the two
mounting screw positions (Fig. 2). Use 3/16 in. bit to drill
holes for anchors. Gently tap anchors into holes until they
are flush to the wall surface. Thread wires through the
center opening of the subbase. Then, mount the subbase
using two screws provided. Gently tighten screws, level top
surface of subbase, then securely tighten screws.

WHEN INSTALLING THIS PRODUCT…

1. Read these instructions carefully. Failure to follow

them could damage the product or cause a hazardous
condition.

2. Check the ratings on the product to make sure the

product is suitable for your application.

3. Installer must be a trained, experienced service tech-

nician.

4. Allow thermostat to warm to room temperature before

operating.

5. After installation is complete, check out product op-

eration as provided in these instructions.

CAUTION

Disconnect power supply to prevent electrical shock
or equipment damage.

IMPORTANT

After wiring is complete, push excess wire back into
the hole, and plug hole with nonhardening caulk,
putty, or insulation to prevent drafts from affecting
thermostat operation.

LOCATION

Install thermostat and subbase about 5 ft. [1.5 m] above

the floor in an area with good air circulation at room
temperature.

Do not install the thermostat where it may be affected

by—

— drafts or dead spots behind doors, in corners, or

under cabinets.

— hot or cold air from ducts.
— radiant heat from sun or appliances.
— concealed pipes and chimneys.
— unheated (uncooled) areas behind the thermostat,

such as an outside wall.

IF REPLACING AN EXISTING THERMOSTAT

Turn power to thermostat off at furnace or boiler. A two

transformer system may require turning off two switches or
disconnects. Remove any existing wallplate or subbase
from wall. Label or write down each wire color with the letter
or number on the wiring terminal as the wire is removed, to
avoid miswiring later.

Fig. 1—Removing thermostat from subbase.

TABLE 1—THERMOSTAT MODELS.

STAGES

SWITCHING

THERMOSTAT

HEAT

COOL

SYSTEM

FAN

APPLICATION

T8621A

1

1

HEAT-AUTO-COOL-OFF

ON-AUTO

Single Stage

T8621C

2

1

HEAT-AUTO-COOL-OFF

ON-AUTO

Multistage

T8621D

2

2

HEAT-AUTO-COOL-OFF

ON-AUTO

Multistage

T8621D

a

2

2

HEAT-OFF-COOL

ON-AUTO

Multistage

a

SUPER TRADELINE model.

HEAT AUTO

COOL OFF

ON

AUTO

FAN

M844

Summary of Contents for T8621A

Page 1: ...surface Thread wires through the center opening of the subbase Then mount the subbase using two screws provided Gently tighten screws level top surface of subbase then securely tighten screws WHEN INSTALLING THIS PRODUCT 1 Read these instructions carefully Failure to follow them could damage the product or cause a hazardous condition 2 Check the ratings on the product to make sure the product is s...

Page 2: ...rews are provided on the back of the thermostat Correct setting of these screws will provide optimum room temperature control NOTE MOST APPLICATIONS WILL NOT REQUIRE A CHANGE IN CYCLE RATE Fig 4 T8621A 1 stage heat 1 stage cool thermostat with HEAT AUTO COOL OFF system and AUTO ON fan switching WIRES THROUGH WALL OPENING WALL WALL ANCHORS 2 SUBBASE MOUNTING HOLES MOUNTING SCREWS 2 M846 FOR STRAIGH...

Page 3: ... SUPPLY 2 1 C2 C1 L1 HOT L2 1 2 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED FOR SINGLE TRANSFORMER SYSTEM JUMPER R AND RC NOMINAL 24 Vac POWER MUST BE PRESENT BETWEEN R AND C FOR THERMOSTAT OPERATION 2 3 3 HIGH LIMIT M1575 SYSTEM TRANSFORMER R C W1 W2 Y2 Y1 G RC FAN RELAY HIGH LIMIT HIGH LIMIT L1 HOT L2 HEAT AUTO COOL SYSTEM SWITCH AUTO ON FAN SWITCH POWER SUPPLY PR...

Page 4: ...3 4 1 2 3 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED FOR GAS OR OIL APPLICATIONS OR ELECTRIC HEAT APPLICATIONS WHERE THE FAN OPERATION IS CONTROLLED INDEPENDENTLY OF THE THERMOSTAT AUTO FAN OPERATES WITH Y1 ONLY TWO TRANSFORMERS MAY BE USED SET SWITCH TO NONELECTRIC POSITION SYSTEM SWITCH FAN SWITCH AUTO ON OFF HEAT COOL STAGE 1 HEAT RELAY STAGE 2 HEAT RELAY STAGE 2 ...

Page 5: ...poweroutage Batteriesare included with thermostat Install batteries in back of thermo stat as shown in Fig 11 Without battery backup the program will remain about 30 seconds in event of power loss IMPORTANT When batteries are first installed the display will flash 1 00 PM and 32 or 0 The temperature display will stay at 32 or 0 until the thermostat is powered from the system wiring Fig 11 Battery ...

Page 6: ...l system power is on check voltage between R and C should be 24 to 30 Vac SETTING DAY AND TIME Restore 24 V power to the thermostat When power is applied to the thermostat the display will read 1 00 PM and roomtemperature Itwillgooffforafewseconds thenbegin to flash on and off Set present day and time Press Press to set the current day Each press of the DAY key advances the display one day Press T...

Page 7: ...ng setting is changed thermostat will wait up to 5 minutes before turning on the cooling equipment This delay protects the compressor Move the system switch to COOL and the fan switch to AUTO Press COOLER key until the setting is about 10 F 6 C below room temperature The cooling equipment and fan should start Press WARMER key until the setting is about 10 F 6 C above room temperature The cooling e...

Page 8: ...y MN 55422 4386 Spain Taiwan United Kingdom U S A CANADA 740 Ellesmere Road Scarborough Ontario M1P 2V9 PRINTED IN TAIWAN R O C QUALITY IS KEY CYCLE RATE SETTING CPH at 50 on time for FIRST stage 1 on 1 heat models DIGIT stage 2 on 2 heat models 0 1 1 3 2 9 3 6 SYSTEM THIRD MANUAL OR AUTO SWITCH DIGIT CHANGEOVER POSITION 0 Manual HEAT or OFF 1 Auto HEAT or OFF 3 Auto AUTO 4 Manual COOL 5 Auto COOL...