Page 1: ...ETN24 PM HP SUPER BL Owner s manual Technician Settings C F Aux ...

Page 2: ...ed Lo Tel 972 3 9626462 Fax 972 3 9626620 support meitavtec com File etn24 pm hp super_operating manual vsd ETN24 PM HP SUPER BL Owner s manual Technician Settings Pg 2 Press and hold the Fan C F button 10 sec to switch between temperature scales Temperature scale Press and hold the On Off button 10 sec to activate deactivate Economy mode Note While in Economy mode the display will alternate betwe...

Page 3: ...pull the back panel out B Line the back panel up against the wall or flat surface Install three screws as required C Make electrical connections as shown on enclosed electrical wiring diagram D Install the cove to the back panel first the two tabs on the bottom and then the top tongue Push until tight against the wall Tel 972 3 9626462 Fax 972 3 9626620 support meitavtec com ETN24 PM HP SUPER BL O...

Page 4: ...OFF External sensor S1 1 S1 3 OFF S1 2 ON ON 1 2 3 4 5 6 ON 1 2 3 4 5 6 2 Fan speeds 1 Fan speed ON 1 2 3 4 5 6 Internal sensor External sensor ON 1 2 3 4 5 6 Compressor delay Use DIP Switch S1 4 to activate the 3 minutes compressor delay as follows Enable compressor delay S1 4 OFF Disable compressor delay S1 4 ON Note During delay the temperature scale symbol C F will flash ON 1 2 3 4 5 6 Enable ...

Page 5: ... flash Use the and buttons to adjust the set point temperature for cooling in economy mode Range 12 32 C 54 90 F Default 28 C 82 F Set point temperature for heating in economy mode Press the Mode button again Heat and Aux will flash Use the and buttons to adjust the set point temperature for heating in economy mode Range 10 30 C 50 86 F Default 30 C 86 F The Open Close time of the valve can be adj...

Page 6: ...the Mode button again to return to normal display Freeze protection control Cont In the event of extremely low indoor temperatures conditions the Freeze protection function will override any existing mode and automatically switch the 1st heating stage ON without indication to user When the room temperature drops below 7 C 45 F the thermostat will switch to heat mode and start the first heating sta...

Page 7: ...Comments Tel 972 3 9626462 Fax 972 3 9626620 support meitavtec com ETN24 PM HP SUPER BL Owner s manual Technician Settings Pg 7 ...

Page 8: ...Tel 972 3 9626462 Fax 972 3 9626620 support meitavtec com ...