Technician settings
Tel: +972-3-9626462
Fax: +972-3-9626620
support@meitavtec.com
ETN24-PM-HP-SUPER-BL
Owner’s manual & Technician Settings
Pg. 6
Temperature display (Set point only or room and set point)
Press the [Mode] button again – “tr” will appear on display.
Use the [+] and [-] buttons to select between:
“tr” + “OFF”
- Set point temperature only
“tr” + “ON”
- Room temperature and set point
Note: In the room and set point option, press the [+] or [-] buttons to
view the set point.
Backlight ON or OFF (the backlight may not be available in all models)
Press the [Mode] button again – “bL” will appear on display.
Use the [+] and [-] buttons to select between:
“ON”
- Back light ON
“OFF”
- Backlight OFF
On/Off or Start/Stop configuration
Press the [Mode] button again – “St” will appear on display.
Use the [+] and [-] buttons to select between:
“ON”
- Unit will remain OFF after an electrical blackout (Start/Stop)
“OFF”
- Unit will return to previous state after an electrical blackout (On/Off)
Press the [Mode] button again to return to normal display.
Freeze protection control
Cont’
In the event of extremely low indoor temperatures conditions, the Freeze
protection function will override any existing mode and automatically switch the
1
st
heating stage ON (without indication to user).
When the room temperature drops below 7°C (45°F), the thermostat will switch to
heat mode and start the first heating stage (valve).
When room temperature returns to 8°C (47°F), freeze protection will turn OFF.
Freeze protection will start when the thermostat is either ON or OFF.
Press the [Mode] button again – “FP” will appear on display.
Use the [+] and [-] buttons to select between:
“FP” + “ON”
- Enable freeze protection
“FP” + “OFF”
- Disable freeze protection
Offset for calibration of measured temperature
Press the [Mode] button again – “OFF” and “SET” will flash.
Use the [+] and [-] buttons to adjust the offset.
Range: -5…+5
°C (-9…+9°F), Default 0°C (0°F).
ON
OFF
ON
OFF
Backlight
ON
Backlight
OFF
Start/Stop
(remains off)
On/Off
(return to
previous state)
Freeze
protection OFF
OFF
S
ET
°C
OFF
S
ET
°F
Offset (°C)
Offset (°F)
Freeze
protection ON
OFF
ON
Room and set
point
Set point only
OFF
ON
°C
°F