M
22
AVTM21-415Ja Rev. A June 2005
POWER SUPPLY OPTION, Catalog No. 210415-47
When this option is supplied, Megger recommends that the
service supply be limited by an appropriate line fuse to provide
protection in case of a malfunction of the stepdown
transformer.
Providing this protection is the responsibility
of the user
.
A fuse of not less than 1¼ amperes or more than
3 amperes is recommended.
Because of the many different service sockets in general use,
the input cable has been provided with a plug for which
adaptors are readily available. If use of an adaptor is not
desirable, the plug supplied can be cut off and replaced with
one best suited to the service conditions. The green lead of the
input cable is to be connected to ground, the white lead to the
supply neutral, and the black lead to the "hot" portion of the
line.
Summary of Contents for ATEC 210415 Series
Page 2: ...15 kV Megohmmeter Test Set Catalog No 210415 Series M...
Page 9: ...M 2 AVTM21 415Ja Rev A June 2005 Figure 1 15 kV Megohmmeter Test Set Catalog No 210415...
Page 13: ...M 6 AVTM21 415Ja Rev A June 2005 M...
Page 19: ...M 12 AVTM21 415Ja Rev A June 2005 M...
Page 23: ...M 16 AVTM21 415Ja Rev A June 2005 Figure 2 Schematic Diagram of the 15 kV Megohmmeter...
Page 30: ...SETTING UP 23 AVTM21 415Ja Rev A June 2005 Figure 4 Testing in a Substation...
Page 32: ...SETTING UP 25 AVTM21 415Ja Rev A June 2005 Figure 6 Testing Transformer Terminals...
Page 33: ...M 26 AVTM21 415Ja Rev A June 2005 Figure 7 DC Motor Test Setup Figure 8 Generator Test Setup...
Page 47: ...M 40 AVTM21 415Ja Rev A June 2005 M...
Page 53: ...M 46 AVTM21 415Ja Rev A June 2005 M...
Page 57: ...M 50 AVTM21 415Ja Rev A June 2005 M...
Page 73: ...M 66 AVTM21 415Ja Rev A June 2005 Figure 15A Interior View Figure 15B Interior View...
Page 75: ...M 68 AVTM21 415Ja Rev A June 2005 M...
Page 81: ...M 74 AVTM21 415Ja Rev A June 2005 M...
Page 82: ...M 2621 Van Buren Avenue Norristown PA 19403 1 800 723 2861 ext 8578 megger com...