output current is limited to 7.5 mA. When such a trip-out
occurs, before approaching the equipment, apply the
grounding stick to the high voltage terminal to discharge the
test setup as all stored energy may not be dissipated by such a
failure.
NORMAL SHUTDOWN PROCEDURE
When the test has been completed, follow this shutdown
procedure:
1.
Set the voltage control to zero.
2.
Open the AC "ON" switch or the OUTPUT "ON" switch
or both.
3.
When the voltmeter indicates that voltage has decreased to
a value of less than half the voltage used during the test,
use an insulated grounding stick to apply a direct short
circuit to all ungrounded terminals of the apparatus being
tested.
4.
Disconnect cables in the following sequence; first, the
input cable; second, the output cable (including the guard
if in use), finally, the ground cable.
5.
Apply ground bonds to the equipment that has been
disconnected.
INTERRUPTING A TEST
At any time, the AC "ON" or HV "ON" switches can be
opened manually to interrupt a test, provided that the
grounding stick is applied afterward to discharge any stored
energy as described in the normal shutdown procedure.
For any circumstances requiring that a test be stopped
immediately, the procedure is to apply the grounding stick
directly to the high-voltage terminal. This action will remove
Summary of Contents for ATEC 210415 Series
Page 2: ...15 kV Megohmmeter Test Set Catalog No 210415 Series M...
Page 9: ...M 2 AVTM21 415Ja Rev A June 2005 Figure 1 15 kV Megohmmeter Test Set Catalog No 210415...
Page 13: ...M 6 AVTM21 415Ja Rev A June 2005 M...
Page 19: ...M 12 AVTM21 415Ja Rev A June 2005 M...
Page 23: ...M 16 AVTM21 415Ja Rev A June 2005 Figure 2 Schematic Diagram of the 15 kV Megohmmeter...
Page 30: ...SETTING UP 23 AVTM21 415Ja Rev A June 2005 Figure 4 Testing in a Substation...
Page 32: ...SETTING UP 25 AVTM21 415Ja Rev A June 2005 Figure 6 Testing Transformer Terminals...
Page 33: ...M 26 AVTM21 415Ja Rev A June 2005 Figure 7 DC Motor Test Setup Figure 8 Generator Test Setup...
Page 47: ...M 40 AVTM21 415Ja Rev A June 2005 M...
Page 53: ...M 46 AVTM21 415Ja Rev A June 2005 M...
Page 57: ...M 50 AVTM21 415Ja Rev A June 2005 M...
Page 73: ...M 66 AVTM21 415Ja Rev A June 2005 Figure 15A Interior View Figure 15B Interior View...
Page 75: ...M 68 AVTM21 415Ja Rev A June 2005 M...
Page 81: ...M 74 AVTM21 415Ja Rev A June 2005 M...
Page 82: ...M 2621 Van Buren Avenue Norristown PA 19403 1 800 723 2861 ext 8578 megger com...