Starting up for the first time
57
12.1.2 Adjusting the boiler controller
The boiler controller must be adjusted to match the changed boiler power rating.
Parameter level 200
Open the menu
Pellematic
at the operating device. Parameter level 200 is exclusively for customer service technicians
and MEco employees. You access parameter level 200 by entering the code in parameter P199. The code for parameter
level 200 is the sum of day plus hour, e.g. : Day:
26
/ 08/ 2009 and hour:
14
:30:47; (26 + 14 = 40) results in the code: 26
+ 14 = 40.
Then go to parameter 265 and adjust the boiler power rating
Para-
meter
Display on screen
Description
Adjus
table
Factory
setting
P265
Power level
P265: level 15
Adjusting the boiler power rating
yes
15/25/36
Note:
The setting for parameter 265 is the factory setting for the boiler power rating
12.2 Settings in the boiler controller
Parameters that you must adjust to the relevant boiler type.
P265
Adjusting the boiler power rating
P263
Setting the boiler setpoint temperature, default 175°F
P202
Setting the switch-off temperature, default 185°F
P212
Activating the de-ashing system, if installed
P270
Activating the flame sensor, if installed (optional)
P213
Activating the level detection system, if weighting cells are installed (optional)
PE 3671 USA 2.3
Installation Manual PES 36–56
Summary of Contents for Pellematic PES 12-20
Page 38: ...Connecting up to the power supply 38 Installation Manual PES 36 56 PE 3671 USA 2 3...
Page 46: ...Connecting up to the power supply 46 Installation Manual PES 36 56 PE 3671 USA 2 3...
Page 47: ...Connecting up to the power supply 47 PE 3671 USA 2 3 Installation Manual PES 36 56...
Page 88: ...Appendix 88 Installation Manual PES 36 56 PE 3671 USA 2 3...
Page 92: ...Appendix 92 Installation Manual PES 36 56 PE 3671 USA 2 3...
Page 99: ...Appendix 99 Labeling 105x74 PE 3671 USA 2 3 Installation Manual PES 36 56...
Page 100: ......