Technical Manual
Glass Room Temperature Controller Smart SCN-RTRGx.02
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
•
Germany
Phone: +49-2263-
880 • [email protected] • www.mdt.de
67
67
Minimum/Maximum levels for Day/Night
The setting for Day/Night switchover is in the "General Settings" menu.
The following parameter settings are available:
ETS-Text
Dynamic range
[Default value]
Comment
Minimum level for Day
Level 0 - Level 4
[Level 0]
Defines the minimum level in
daytime operation.
Maximum level for Day
Level 0 - Level 4
[Level 4]
Defines the maximum level in
daytime operation.
Minimum level for Night
Level 0 - Level 4
[Level 0]
Defines the minimum level in
Night mode.
Maximum level for Night
Level 0 - Level 4
[Level 4]
Defines the maximum level in
Night mode.
Table 70: Settings
–
Minimum/Maximum levels for Day/Night
With the Day/Night switchover and the associated minimum/maximum output level, the ventilation
control can be limited. If, for example, the fan is only to run at level 2 in “Night”
-mode to keep the
noise level of the ventilation low or to avoid draughts, this can be realised with this parameter.
The following table shows the communication objects for Day/Night switching:
Number Name/Function
Length
Usage
88
Day/Night
1 Bit
Switching between Day/Night operation
Table 71: Communication object
–
Day/Night switchover