Technical Manual
Glass Push-button II Smart & Push-button Smart 86 [Series .02]
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1 • Germany
Phone: +49-2263-
880 • [email protected] • www.mdt.de
51
51
The following table shows the available settings:
ETS-Text
Dynamic range
[Default value]
Comment
Button assignment
(left/right)
▪
next / previous
▪
previous / next
Only for two-button function.
Setting in which direction to
switch when the left/right
button is pressed.
Number of values
▪
2
▪
3
▪
4
Setting between how many
values are to be switched.
Datapoint type
▪
2 Bit DPT 2.001 Switch Control
▪
1 Byte DPT 5.001 Percent
(0…100%)
▪
1 Byte DPT 5.005
Decimal factor (0…255)
▪
1 Byte DPT 17.001 Scene number
▪
2 Byte DPT 7.600
Colour Temperature (Kelvin)
▪
2 Byte DPT 9.001 Temperature (°C)
▪
2 Byte DPT 9.004 Brightness (Lux)
▪
3 Byte DPT 232.600
RGB
Value 3x(0…255)
Setting the type of datapoint to
be sent.
1.-4. Toggle value
any value according to set datapoint type Setting the respective value for
the toggle value.
Time delay between
value switchovers
no delay
1 s
–
10 s
Setting a delay between
sending the toggle values.
Long keypress
▪
not active
▪
active
Activating a function with a long
keystroke.
Action on left/right
button
▪
1.-4. Toggle value
▪
4. Toggle value if last 1. Toggle
value, otherwise 1.
.
Toggle value
▪
Send
“
0
”
▪
“O
FF
” to second object
▪
“O
N
” to second object
Only for two-button function!
Setting the action with long
keystroke.
Number of possible switching
values according to the
selection "Number of values"
.
Action on long
keypress
▪
1.-4. Toggle value
▪
4. Toggle value if last 1. Toggle
value, otherwise 1.
.
Toggle value
▪
Send
“
0
”
▪
“O
FF
” to second object
▪
“O
N
” to second object
Only for single-button
function.
Setting the action with long
keystroke.
Number of possible switching
values according to the
selection "Number of values"
Time for long
keypress
Basic setting
0,1 s
–
30 s
Setting of a time from when a
long keystroke is detected.
Switching type
▪
Limit stop
(after the last value,
this is repeated)
▪
Overrun (after the last value, the
first value is sent again)
Only for two-button function.
Setting what should happen
when the last switching value is
reached.
Table 33: Settings
–
Send Values - Subfunction: Toggle values/scenes (up to 4 values)