5.2.7 Priority/Forced control
The following figure shows the parameter priority/forced control:
Figure 12: Priority/Forced control
The following settings are available:
ETS-text
Dynamic range
[default value]
comment
Priority/Forced Control
not active
2 Bit forced control
1 Bit priority ON
1 Bit priority OFF
Activation of the forced
control/priority function
Release time for forced
control (0 = not active)
0-600min
[0 min]
Activation of a release time
from the priority/forced
control into the normal state.
Behavior after forced
control/priority
On
Off
no change
previous state, catch up
on switching
previous state
Setting of the behavior after
deactivating priority/forced
control.
Table 15: Priority/Forced control
The priority/forced operation cause the priority switching of output. By using the release time, the
priority/forced control can be deactivated automatically and the channel changes into the normal
state.
The followings actions can be performed after deactivating the priority/forced control:
no change
The channel stays in the current state.
On
The channel is switched on.
Off
The channel is switched off.
previous state, catch up on switching
The channel restores the state before locking in compliance with the last switching command,
which was sent during the channel was locked.
previous state
The channel restores the state before locking.
The following table shows the communication object:
Number
Name
Length
Usage
5
Forced control/Priority
1 Bit
Activation/Deactivation of the forced
control/priority
Table 16: Communication object priority/forced control