8. APPENDIX
GENERAL
Type
Unit
Default
Min
Max
Resolution
0
2
1
G1
Model
O=Chiller,
1=Heat Pump,
2=Chiller/ Boiler,
3=Heat pump/Boiler, 4=Boiler,
5=Heat pump+Boiler
F
Flag
4
(Boiler)
G2
Number of compressor
1=1 compressor,
2=2 compressor
3=3 compressor,
4=4 compressor
F
Flag
1
1
4
1
G3
On/off input
0=disable, 1=enable
F
Flag
0 (disable)
0
1
1
G4
Cool/Heat input
0=disable, 1=enable
F
Flag
0 (disable)
0
1
1
G5
External alarm input
0=disable, 1=enable
F
Flag
0 (disable)
0
1
1
G6
Water system for chiller network
0=independent, 1=modular
F
Flag
0 (disable)
0
1
1
G7
Unit number
F
Flag
0
0
50
1
SENSOR
Type
Unit
Default
Min
Max
Resolution
S1
Entering water sensor calibration
U
ºC ( F)
0 (0)
-12 ( 2 1 6 )
12 (21.6)
0.1
S2
Leaving water sensor calibration
U
°C (°F)
0 (0)
-12 (-21.6)
12 (21.6)
0.1
S3
Air sensor calibration
U
°C (°F)
0 (0)
-12 (-21.6)
12 (21.6)
0.1
S4
Defrost (condenser) sensor 1 calibration
U
°C (°F)
0 (0)
-12 (-21.6)
12 (21.6)
0.1
S5
Defrost (condenser) sensor 2 calibration
U
°C (°F)
0 (0)
-12 (-21.6)
12 (21.6)
0.1
S6
Defrost (condenser) sensor 3 calibration
U
°C (°F)
0 (0)
-12 (-21.6)
12 (21.6)
0.1
S7
Defrost (condenser) sensor 4 calibration
U
°C (°F)
0 (0)
-12 (-21.6)
12 (21.6)
0.1
S8
Compressor discharge sensor 1 calibration U
°C (°F)
0 (0)
-12 (-21.6)
12 (21.6)
0.1
S9
Compressor discharge sensor 2 calibration U
°C (°F)
0 (0)
-12 (-21.6)
12 (21.6)
0.1
S 10
Compressor discharge sensor 3 calibration U
°C (°F)
0 (0)
-12 (-21.6)
12 (21.6)
0.1
S11
Compressor discharge sensor 4 calibration U
°C (°F)
0 (0)
-12 (-21.6)
12 (21.6)
0.1
REGULATOR
Type
Unit
Default
Min
Max
Resolution
R1
Cooling set-point
D
°C (°F)
12 (53.6)
R5
R6
0.1
R2
Cooling differential
U
°C (°F)
1.5* (2.7)
0.4 (0.7)
10(18)
0.1
R3
Heating set-point
D
°C (°F)
40 (104)
R7
R8
0.1
R4
Heating differential
U
°C (°F)
1.5* (2.7)
0.4 (0.7)
10 (18)
0.1
R5
Minimum Cooling set-point
U
°C (°F)
7 (44.6)
-20 (-4)
R6
1
R6
Maximum Cooling set-point
U
°C (°F)
20 (68)
R5
40 (104)
1
R7
Minimum Heating set-point
U
°C (°F)
30 (86)
-20 (-4)
R8
1
R8
Maximum Heating set-point
U
°C (°F)
50 (122)
R7
90 (194)
1
R9
Auxiliary heater set-point (threshold below
heating set-point)
U
°C (°F)
5 (9)
0 (0)
40 (72)
0.1
R10
Auxiliary heater differential
U
°C (°F)
2 (3.6)
0.4 (0.7)
10 (18)
0.1
R11
Auto boiler set-point (threshold below heating
set-point)
U
°C (°F)
5 (9)
0 (0)
40 (72)
0.1
R12
Auto boiler differential
U
°C (°F)
2(3.6)
0.4 (0.7)
10(18)
0.1
R13
Auto boiler start time threshold
U
min
30
0
199
1
COMPRESSOR
Type
Unit
Default
Max
Min
Resolution
C1
Compressor minimum run time
U
sec
120
0
1990
10
C2
Compressor minimum stop time
U
sec
180
0
1990
10
C3
Time interval between two starts
U
sec
450
0
1990
10
C4
Start delay between two compressors
U
sec
15
0
199
1
C5
Pump on
ĺ
compressor on delay
U
sec
180
0
1990
10
C6
Comp off
ĺ
pump off delay
U
sec
60
0
199
10
C7
Discharge cut-off set-point
U
°C
120 (248)
0 (32)
150 (302)
1
CONDENSER DEFROST
Type
Unit
Default
Max
Min
Resolution
D1
Start defrost temperature
U
°C (ºF)
0 (32)
-20 (-4)
D2
1
D2
End defrost temperature
U
°C (ºF)
14 (57)
D1
40 (104)
1
34
Summary of Contents for M4AC 080 C
Page 10: ...5 2 Menu Structure Menu Structure Diagram for Chiller 9...
Page 49: ...Outlines and Dimensions Model M4AC MAC080 100 C CR 48...
Page 50: ...Model M4AC MAC120 150 C CR 49...
Page 52: ...Wiring Diagrams Model M4AC MAC080 100 120 150C Isolator Switch 51...
Page 53: ...Model M4AC MAC080 100 120 150C Terminal Block 52...
Page 54: ...Model M4AC MAC080 100 120 150CR Isolator Switch 53...
Page 55: ...Model M4AC MAC080 100 120 150CR Terminal Block 54...
Page 68: ...2004 McQuay International 1 800 432 1342 www mcquay com ISO 9002 REGISTERED...