Parameter
Value
Description
Normal
Turn ON backlight for 30s via key press
Backlight
Always
Always ON backlight
ON
Enable beeping sound when fault/ alarm occurred
Buzzer
OFF
Disable beeping sound when fault / alarm occurred
Enable
Show screen saver when timeout
* Screen Saver
Disable
No screen save
* Timeout
1 – 30m
Timeout for showing screen saver
Contract
0 – 100%
Adjust the contrast setting for the LCD panel
OFF
No backlight
Brightness
Low, Medium, High
Adjust the backlight intensity
ºC
Display temperature in degree Celsius
Temp Unit
ºF
Display temperature in Fahrenheit
* This product must be branded. Screen saver will be deactivated for brand less panel
6.3 CMOS Reset
x
CMOS reset allows user to reset some settings to default value such as:
Password
-> 0001
Backlight
-> Normal
Buzzer
-> ON
Screen Saver
-> Disable
Timeout
-> 5m
Contrast
-> 50%
Brightness
-> Medium
Temp Unit
-> ºC
x
Procedures
1. Power OFF the panel
2. Close the jumper JH2 with the provided jumper header
3. Power ON the panel and the LCD panel should display as follow:
CMOS is resetting ……….
CMOS reset completed!
Please remove JUMPER
and restart the panel
4. Remove the jumper header (put the jumper header on 1 pin only), power OFF and then power ON the panel.
32
Summary of Contents for M4AC 080 C
Page 10: ...5 2 Menu Structure Menu Structure Diagram for Chiller 9...
Page 49: ...Outlines and Dimensions Model M4AC MAC080 100 C CR 48...
Page 50: ...Model M4AC MAC120 150 C CR 49...
Page 52: ...Wiring Diagrams Model M4AC MAC080 100 120 150C Isolator Switch 51...
Page 53: ...Model M4AC MAC080 100 120 150C Terminal Block 52...
Page 54: ...Model M4AC MAC080 100 120 150CR Isolator Switch 53...
Page 55: ...Model M4AC MAC080 100 120 150CR Terminal Block 54...
Page 68: ...2004 McQuay International 1 800 432 1342 www mcquay com ISO 9002 REGISTERED...