4. INSTALLATION
4.1 Chiller Bus
Supported up to 50 units of Chiller
Chiller 0
Chiller 1
Chiller 2
5 way wire (CN8)
Chiller
Communication bus
Chiller Panel 1
(Slave)
Chiller Panel 0
(Master)
CHILLER NETWORK
Chiller panel needs to be energized with +12Vdc. The 5 way wires that provided is once on the easiest solution to
establish a communication between the panel and chiller main board (CN8-CN8). If the 5-way wires socket has been
occupied in main board, just using 2 insulation wires connected to the +12Vdc and GND terminal block from main
board to panel can still energize a panel. Beside that, another 2 insulation wired are needed to establish a
communication between panel and chiller main board.
Chiller panel can support maximum up to 50 units of chiller. In the chiller network, duplication of main board unit
address is not allowed. Each chiller main board should have their unique unit address (0 – 50).
For first time running, user need to assign a unique unit address to each main board in the chiller network. User
should follow the procedure below:
x
Only power ON one main board at once time. Make sure not others main boards are energized.
x
By using the panel connected to the main board.
<ENTER>
<ENTER>
Summary Pages
Main Menu
Settings Menu
1. General
Set Parameter
G7 Unit No
<ENTER>
<ENTER>
Key in “0001” as
password
<ENTER>
x
Key in a unique unit address and press ENTER to execute.
x
De-energized the main board and repeat the procedures again until all the main boards have been assigned a unique unit
address
IMPORTANT: Do not assign a same unit address to more than one chiller main board.
RECOMMENDATION: Please select a coherent model (G1 Model) to all the chiller main boards in the same
network
6
Summary of Contents for M4AC 080 C
Page 10: ...5 2 Menu Structure Menu Structure Diagram for Chiller 9...
Page 49: ...Outlines and Dimensions Model M4AC MAC080 100 C CR 48...
Page 50: ...Model M4AC MAC120 150 C CR 49...
Page 52: ...Wiring Diagrams Model M4AC MAC080 100 120 150C Isolator Switch 51...
Page 53: ...Model M4AC MAC080 100 120 150C Terminal Block 52...
Page 54: ...Model M4AC MAC080 100 120 150CR Isolator Switch 53...
Page 55: ...Model M4AC MAC080 100 120 150CR Terminal Block 54...
Page 68: ...2004 McQuay International 1 800 432 1342 www mcquay com ISO 9002 REGISTERED...