44
OM
AGSB-5
SET UNIT SPs
(2)
Available Modes = COOL
Select w/Unit Swt. Off
SET UNIT SPs
(3)
Cool LWT =
XX.X
°
F
Ice LWT – XX.X
°
F
The unit will only use the setpoint for the Mode selected.
SET UNIT SPs
(4)
StartDelta= XX.X
°
F
StopDelta= XX.X
°
F
StageDelta= XX.X
°
F
The StartDelta is the number of degrees above the chilled water setpoint the water
temperature must rise for a compressor to start when no compressors are running. The
default is 10 degrees. F., the range is 0 to 10 degrees. F. Settings below 10 degrees will
have the undesirable effect of increasing compressor cycling.
The StopDelta is the number of degrees below the chilled water setpoint the water
temperature must fall for the last compressor to stop.
The StageDelta is the number of degrees change in the chilled water to initiate a change in
staging.
SET UNIT SPs
(5)
Max Pulldn=X.X
°
F/min
EvapRecTimer=XXX sec
Evap Pump= #1,#2, Auto
The controller can start either of two chilled water pumps or in the Auto mode will
automatically select the pump with the least run hours.
SET UNIT SPs
(6)
Reset Type =none
MaxResetDT =XX.X
°
F
StrtResetDT=XX.X
°
F
See page 30 for reset options.
SET UNIT SPs
(7)
Soft Load
= Off
Begin Capacity= XXX%
SoftLoadRamp= XXmin
See page 17 for soft load and demand limit options.