Table 13, Unit Controller Setpoints
Description Default Range
PW
Unit
Unit Enable
OFF
OFF, ON
O
Unit Mode
COOL
COOL, COOL w/Glycol,
ICE w/Glycol, TEST
O
Control source
SWITCHES
SWITCHES, KEYPAD, NETWORK
O
Available Modes
COOL
COOL, COOL w/Glycol, COOL/ICE
w/Glycol, ICE w/Glycol, TEST
M
Cool LWT
44. 0
°
F 25.0(40.0)
to
60.0
°
F
O
Ice LWT
25.0
°
F 20.0
to
38.0
°
F
O
Startup Delta-T
10.0 degF
0.0 to 10.0 degF
O
Stop Delta-T
3.0 degF
0.0 to 3.0 degF
O
Stage Delta-T
2.0 degF
0.0 to 3.0 degF
O
Max Pulldown
0.5 degF/min
0.1-5.0 degF/min
M
Evap Recirculate
30 sec
0 to 300 sec
M
Evap pump control
#1 Only
#1 Only, #2 Only, Auto
M
LWT Reset Type
NONE
NONE, RETURN, 4-20mA, OAT
M
Max Reset
0.0 degF
0.0 to 20.0 degF
M
Start Reset Delta-T
10. 0 degF
0.0 to 20.0 degF
M
Soft Load
On
On, Off
M
Begin Capacity Limit
40%
20-100%
M
Soft Load Ramp
20 min.
1-60 min.
M
Demand Limit
no
No,yes
M
Low Ambient Lock
55
°
F
35-70 degF
M
Ice Time Dlay
12 hrs.
1-23 hrs.
M
Clear ice Timer
No
No, Yes
M
Display Units
°
F, psi
°
F, psi
M
Language English
English
M
BAS Protocol
NONE
NONE, BACnet, LonWorks,
CAREL, MODBUS, N2
M
Ident number
1
0=200
M
Baud Rate
19200
1200, 2400, 4800, 9600, 19200
M
Compressors
Sequence # Cir 1
1
1-3
M
Sequence # Cir 2
1
1-3
M
Sequence # Cir 3
1
1-3
M
Max Compressors On
3
1-3
M
Start-start timer
20 min
15-60 minutes
M
Stop-start timer
5 min
3-20 minutes
M
Number of Compressors
2
2-3
M
Pumpdown pressure
25.0 psi
10.0-30.0 psi
M
Pumpdown time limit
120 sec
0-180 sec
M
Light Load Stage Down Point
255
20-50% Slide
M
Light Load Stage Down Delay
3 min.
3-30 min.
M
Stage Up Delay
5 min.
0-60 min.
M
Alarms
Low Evap Pressure-Unload
28 psi
0 to 45 psi
M
Low Evap Pressure-Hold
30 psi
0 to 45 psi
M
Low Oil Level Delay
120 sec
10-180 sec
M
High Oil Press Diff Delay
15 sec
0-60 sec
M
Min Lift Delay
30 sec
10-120 sec
M
Low Subcooling
5 degF
0 to 10 degF
M
High Discharge Temperature
200
°
F
150 to 200 F
M
Evaporator Water Freeze
36
°
F 15(34)
to
42
°
F
M
Evap Flow Proof
3 sec
3 to 120 sec
M
High Lift Delay
5 sec.
0-30 sec.
M
Sensors
OAT sensor offset
0 degF
-5.0 to 5.0 degF
M
LWT sensor offset
0 degF
-5.0 to 5.0 degF
M
EWT sensor offset
0 degF
-5.0 to 5.0 degF
M
These parameters are remembered during power off, and are factory set to the
Default
value.