background image

4.4 Shutdown procedure

 

On compressors using gasoline drive, close hand lever on carburetor and turn "On/Off" switch off. 
Close fuel cylinder valve and drain condensate out of compressor. In addition, check oil level of 
compressor, gasoline level in engine tank and carry out current service (§ 4.8). 

 

4.5 Preparation for extended storage

 

Prior to extended storage, the compressor should run a few minutes against a small backpressure of 
approximately 300PSI (20 bar), by partly closing filling valve in order to prevent possibility of corrosion. 
Open condensate drain valve again, then close them to prevent loss during transportation. 

 

4.6 Preservation of compressor

 

Remove intake air filter cartridge. Start compressor and slowly fill 10 to 20 cm3 of MAXLUBE 501 
synthetic oil into intake piece of compressor. Keep filling valve open and condensate drain valve 
closed. Operate unit for approximately 1 minute. Close filling valves and open condensate drain valves. 
Decompress all stages and then close all valves. 

In cases of prolonged storage periods, run unit every 3 months. Lubricating oil loses its efficiency 
during prolonged idle periods in the compressor and motor. This requires draining and replacing with 
fresh oil at least once a year. 

 

4.7 Maintenance and air tightness test

 

Besides the standard stipulated service works (§ 4.8) we recommend you clean the compressor at 
regular intervals to notice any oil leakage and impairment to the efficiency of the cooling system 
resulting from dirt on cooler coils and fins. Test air tightness by regularly brushing all fittings, valves and 
tubing of the condensate drain with soap-water or with leak test spray. 
Air leaks considerably impair the output of the compressor. 

 

4.8 Service, service timetable 

 

4.8.1 Oil level check, change of oil

 

Check oil level daily before putting the unit into operation. Oil level must be between minimum and 
maximum of transparent tube on the crankcase, behind the filter or on the front, oil level sight glass for 
cabinet models.  Oil level must not be too high because excessive oil can result in over-lubrication and 
coking of the valves. When oil level is too low, oil thrower pins do not any longer dip into oil, lubrication 
stops and the unit is destroyed. 

Oil change:

 first oil change after 15 operating hours, further oil changes every 50 operating hours. If 

the operating hours indicated above are not reached within 5 months, oil must be changed after the 
season or before storing for the winter. Do not use oils of different brands at the same time: do not use 
openly stored oil, but only from original oilcans. 

 

 

 

 

Page 7 of 22

Summary of Contents for 90 PBAC

Page 1: ...vice max air com Max Air is a registered trademark with the U S patent office copyright 2006 This manual cannot be reproduced without the express written permission of Max Air WARNING DO NOT USE WITH...

Page 2: ...lling compressor you are now a filling station You must follow all local state and federal regulations Prior to filling a cylinder check the pressure rating and current hydro date stamped on cylinder...

Page 3: ...e year from purchase date Weight 276 lbs 125kg w 9 HP Honda engine Dimensions 42 L x 20 W x 28 5 H MAX AIR 90 9 0cfm TECHNICAL DESCRIPTION Model Approx output MAX AIR 90 260 L min 9 0cfm Drive motors...

Page 4: ...small particles of lubricating oil This condensate is a milky fluid and precipitates in the separators 2 3 Technical details of the compressor Block 2 3 1 Crankcase crankshaft piston cylinder The cran...

Page 5: ...and optimum separation 2 4 Base Frame Protective Frame Covers Depending on the specifications of the buyer the compressor rests on a base frame consisting of welded section steel with an additional f...

Page 6: ...or disconnect at the power source prior to any work Never weld high pressure tubing Never empty air cylinders completely The closed cylinder should always contain some residual pressure in order to av...

Page 7: ...set pressure relief blow off on the final stage is usually 10 above the cylinder rated pressure Example if you are filling a 3000 psi rated cylinder you should close the fill valve or shut off the com...

Page 8: ...with fresh oil at least once a year 4 7 Maintenance and air tightness test Besides the standard stipulated service works 4 8 we recommend you clean the compressor at regular intervals to notice any o...

Page 9: ...e sure that the holding spring on top is installed properly Only use original cartridges 4 8 5 Condensate drain system Condensate water oil vapors emulsion The color of this emulsion should be milky w...

Page 10: ...be carefully treated to prevent even the slightest damage Use only gasoline soft brushes of copper or nylon Do not use steel brushes screwdrivers etc Should you detect even the smallest damage rupture...

Page 11: ...ty valves must be replaced as complete parts 4 9 1 Cylinders When removing and replacing cylinders note that the piston is in the top position must be on the same level with the cylinder top edge Corr...

Page 12: ...w thread max hex screw M 6 1 0 kpm 7 ft lbs inner hex Screw hex screw M 8 2 5 kpm 18 ft lbs inner hex Screw hex screw M 10 4 5 kpm 32 ft lbs inner hex screw Valve head screw requires torque wrench tig...

Page 13: ...rrect Blocked cooling tubes or Tighten or replace gaskets leaking Check brush with soap replace Intake filter blocked Replace Intake hose bent Readjust Worn pistons or rings Replace Oil taste in deliv...

Page 14: ...elief valve factory preset to customer requirement 11 Front bearing cover 22 Check valve INSIDE upper separator 12 Fan wheel 23 Oil fill vent cap screw 13 Oil filler cap 24 Oil level indicator behind...

Page 15: ...n fold back flat prior to screw down housing cap C Read and remove tape c D Remove snap out plastic plug under tape E Remove plastic plug make sure internal O ring is present and lubricated use silico...

Page 16: ...H E Close up view of plastic plug E at bottom of cartridge B C D I J F G B C D E K H 27 x 2 dia E A Sealed Foil envelope not shown Part Number LF 65247 35 000 cft 72o F 5000psi Page 15 of 22...

Page 17: ...d for any sign of moisture F Warning label read and understand this and any labels on the filter G Molecular sieve beige beads removes humidity H Hopcalite catalyst converts trace amounts of carbon mo...

Page 18: ...14 1 4 x 1 3 4 dia A C E G I B D F H J Part Number LF 1002 10 000 cft 72o F 5000psi NOTE Dimensions exclude threaded plastic nipple w O ring Page 17 of 22...

Page 19: ...s USAGE The detection disc is specially treated to prolong its life A color change from tan to dark grey will occur in the presence of carbon monoxide The rate if change of color is directly related t...

Page 20: ...ly 4 Install window 3 with smooth small diameter against O ring 4 5 Insure window 3 is fully against shoulder of cap 2 6 Avoid spring or other hard objects touching window 7 Install so both elements c...

Page 21: ...ING BLUE Page 20 of 22 Remove top half of element housing and invert Place the blue moisture indicator down inside element against the glass taking care not to touch the blue element with your fingers...

Page 22: ...be carried out in compliance with the instructions contained in this manual Should the required work not be covered by the manual or assistance be required you are advised to contact Max Air directly...

Page 23: ..._______ _________________________________________________________________________________ _________________________________________________________________________________ ____________________________...

Reviews: