CAUTION
Never disconnect the test leads when the message
"MEASURING"
is
displayed.
At the end of the test
the instrument emits a
double sound signal
indicating that the test
is correctly
terminated
and
displays the values
alongside.
LOOP
05.06.01
Value of phase to Earth
Resistance expressed in
Ω
.
1.07
Ω
215A
Freq=50.0HZ
VP-N=231V Vp-PE=231V
P-PE
Value of the phase to Earth
prospective short circuit
current expressed in Ampere
calculated according to the
following formula.
FUNC Z2
Ω
Working mode
Formula for calculation of prospective short circuit current:
PE
N
CC
Z
U
I
=
Where U
N
= Nominal phase to neutral voltage =
127 if V
meas
≤
150
230 if 150V< V
meas
≤
250
This result can be stored pressing the
SAVE
key
twice
(according to paragraph 9.1).