VR2250
Page 19 of 131
In case that:
R
CALIBRATION
>R
MEASURED
the instrument displays
the screen alongside.
LOW
Ω
05.06.01
0.00
Ω
R+ R-
0.00
Ω
0.00
Ω
219mA 219mA
CAL > RES
AUTO 0.11
Ω
ATTENTION:
R
CALIBRATION
>R
MEASURED
FUNC
CAL
THE PREVIOUS RESULTS CANNOT BE SAVED
.
If the value of
Resistance is higher
than 5
Ω
(but lower than
99.9
Ω
)
the instrument
emits a long sound
signal
and displays one
screen similar to the
screen alongside
LOW
Ω
05.06.01
Resistance value higher
than 5
Ω
5.17
Ω
R+ R-
5.17
Ω
5.17
Ω
209mA 209mA
AUTO 0.11
Ω
Test current
FUNC
CAL
The displayed result can be stored pressing the
SAVE
key
twice
(according to
paragraph 9.1).
If the value of
Resistance is higher
than 99.9
Ω
the
instrument emits
a long
sound signal
and
displays the screen
alongside.
LOW
Ω
05.06.01
Resistance value higher
than 99.9
Ω
>99.9
Ω
R+ R-
-.--
Ω
-.--
Ω
---mA ---mA
AUTO 0.11
Ω
ATTENTION:
Value of
Resistance Out of Range
FUNC
CAL
The displayed result can be stored pressing the
SAVE
key
twice
(according to
paragraph 9.1).