Tamper terminal block
The concentrator module has an internal long lever microswitch for tamper protection of the
container. If you use mode of operation on bus, the device will indicate tampering with the
control unit via BUS.
In standalone mode, you can use the terminal block for connection to any burglar alarm or
signaling device (telephone dialer, radio, etc. ..). In this case we must remove the jumpers JP2
and JP5.
Note: Both in the operation on bus, both in stand-alone, after the installation and
testing of the concentrator, we must remove the jumper on the external tamper
terminal block. Leaving the jumper connected to the terminal, the tamper will remain
inactive.
Installation and Programming Manual V1.2
10