DISCHARGE PRESSURE HIGH CHECKLIST
Improper Installation
•
Refer to “Installation/Visual Inspection Checklist”
Restricted Condenser Air Flow
•
High inlet air temperature
•
Condenser discharge air re-circulation
•
Dirty condenser fins
•
Defective fan motor
Improper Refrigerant Charge
•
Overcharged
•
Non-condensable in system
•
Wrong type of refrigerant
Other
•
High side refrigerant lines/component restricted
(before mid-condenser)