HARVEST CYCLE DIAGNOSTICS QUIETQUBE ®
REMOTE CONDENSING UNIT
The headmaster control valve diverts the compressor
discharge gas to the ice machine receiver in the
harvest cycle. All refrigerant flow through the
condenser in the harvest cycle stops. Symptoms of a
headmaster valve that will not seat 100% closed
(completely bypass the condenser) in the harvest
cycle are:
•
Freeze cycle suction and discharge pressure are
normal.
•
The control board indicates safety limit #2. The
failure seems to be temperature related. Example:
The ice machine may function correctly at
temperatures above 32°F but fails at temperatures
below 32°F.
•
Harvest cycle suction pressure is low.
•
Harvest cycle discharge pressure is normal or
slightly low.
Procedure
1. Freeze cycle operation must be normal before
diagnosing the headmaster in the harvest cycle.
(Refer to Cycle Times/24 hr Ice Production/
Refrigerant Pressure Chart)
2. Allow the ice machine to run a normal freeze
cycle (do not initiate an early harvest cycle).
3. At the start of the harvest cycle feel the
compressor discharge line and the liquid line to
the ice machine receiver at the headmaster valve.
The temperature of both lines will be highest at
the beginning of the harvest cycle and then
decrease. Compare the lines 30 seconds into the
harvest cycle and then refer to Harvest Cycle
Headmaster Control Valve Failure List page 198.
Indigo_Model_Tech.book Page 202 Monday, February 20, 2012 1:17 PM
Summary of Contents for QuietQube Indigo Series
Page 2: ......
Page 22: ...22 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Page 36: ...36 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Page 60: ...60 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Page 110: ...110 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Page 115: ...Part Number STH026 2 12 115 This Page Intentionally Left Blank ...
Page 116: ...116 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Page 157: ...Part Number STH026 2 12 157 This Page Intentionally Left Blank ...
Page 158: ...158 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Page 197: ...Part Number STH026 2 12 197 This Page Intentionally Left Blank ...
Page 209: ...Part Number STH026 2 12 209 This Page Intentionally Left Blank ...
Page 216: ...216 Part Number STH026 2 12 USING PINCH OFF TOOL ...
Page 220: ...220 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Page 233: ...Part Number STH026 2 12 233 I0670C I0870C I1070C I1270C QuietQube Remote Air cooled 1 3 Ph ...
Page 234: ...234 Part Number STH026 2 12 IB0690C IB0890C IB1090C QuietQube Remote Air cooled 1 3 Ph ...
Page 235: ...Part Number STH026 2 12 235 II1400 I1800 I2170 QuietQube Remote Air cooled 1 3 Ph ...
Page 236: ...236 Part Number STH026 2 12 ICVD2095 QuietQube Remote Air cooled 3 Ph ...
Page 243: ...Part Number STH026 2 12 243 This Page Intentionally Left Blank ...
Page 244: ...244 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Page 245: ...Part Number STH026 2 12 245 This Page Intentionally Left Blank ...
Page 246: ...246 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Page 247: ......