200
Part Number STH026 2/12
Diagnostics
FREEZE CYCLE - QUIETQUBE® REMOTE
CONDENSING UNIT
1. Determine if the coil is clean.
2. Determine the air temperature entering the
condenser.
3. Determine if the head pressure is high or low in
relationship to the outside temperature. (Refer to
the proper “Cycle Times/24-Hour Ice Production/
Refrigerant Pressure Charts” page 221).
4. Determine the temperature of the liquid line
entering the receiver by feeling it. This line is
normally warm; “body temperature.”
5. Using the information gathered, refer to the chart.
NOTE:
A head pressure control valve that will not
bypass, will function properly with condenser air
temperatures of approximately 70°F (21°C) or above.
When the temperature drops below 70°F (21°C), the
head pressure control valve fails to bypass and the ice
machine malfunctions. Lower ambient conditions can
be simulated by rinsing the condenser with cool water
during the freeze cycle.
Condition
Probable
Cause
Corrective
Measure
Discharge Pressure - High
Liquid Line Temperature -
Hot
Valve stuck in
bypass
Replace
valve
Discharge Pressure - Low
Liquid Line Temperature -
Cold
Valve not
bypassing
Replace
valve
Discharge Pressure - Low
Liquid Line Temperature -
Hot
Ice Machine
Low on
Charge
Refrigerant
Charge
Verification
Indigo_Model_Tech.book Page 200 Monday, February 20, 2012 1:17 PM
Summary of Contents for QuietQube Indigo Series
Page 2: ......
Page 22: ...22 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Page 36: ...36 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Page 60: ...60 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Page 110: ...110 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Page 115: ...Part Number STH026 2 12 115 This Page Intentionally Left Blank ...
Page 116: ...116 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Page 157: ...Part Number STH026 2 12 157 This Page Intentionally Left Blank ...
Page 158: ...158 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Page 197: ...Part Number STH026 2 12 197 This Page Intentionally Left Blank ...
Page 209: ...Part Number STH026 2 12 209 This Page Intentionally Left Blank ...
Page 216: ...216 Part Number STH026 2 12 USING PINCH OFF TOOL ...
Page 220: ...220 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Page 233: ...Part Number STH026 2 12 233 I0670C I0870C I1070C I1270C QuietQube Remote Air cooled 1 3 Ph ...
Page 234: ...234 Part Number STH026 2 12 IB0690C IB0890C IB1090C QuietQube Remote Air cooled 1 3 Ph ...
Page 235: ...Part Number STH026 2 12 235 II1400 I1800 I2170 QuietQube Remote Air cooled 1 3 Ph ...
Page 236: ...236 Part Number STH026 2 12 ICVD2095 QuietQube Remote Air cooled 3 Ph ...
Page 243: ...Part Number STH026 2 12 243 This Page Intentionally Left Blank ...
Page 244: ...244 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Page 245: ...Part Number STH026 2 12 245 This Page Intentionally Left Blank ...
Page 246: ...246 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Page 247: ......