Safety Limits
Refer to “Analyzing Safety
Limits” page 112 to eliminate
all non-refrigeration
problems.
Stops on safety limit:
1 or 2
Stops on safety limit:
1 or 2
Stops on safety limit:
1 or 2
Stops on safety limit:
1
Freeze Cycle
Discharge Pressure
_______ ______ ______
1 minute Middle End
into cycle
If discharge pressure is High or Low refer to freeze cycle high or low discharge pressure
problem checklist page 141 & page 142 to eliminate problems and/or components not listed on
this table before proceeding.
Freeze Cycle
Suction Pressure
_______ ______ _____
1 minute Middle End
If suction pressure is High or Low refer to freeze cycle high or low suction pressure problem
checklist page 144 & page 145 to eliminate problems and/or components
not listed on this table before proceeding.
Suction pressure is
High
Suction pressure is
Low or Normal
Suction pressure is
Normal or High
Suction pressure is
High
Harvest Valve
Audible refrigerant flow
through left or right valve
in Freeze cycle
No audible
refrigerant flow through
left or right valve in
Freeze cycle
No audible
refrigerant flow through
left or right valve in
Freeze cycle
No audible
refrigerant flow through
left or right valve in
Freeze cycle
I Model QuietQube® Single Expansion Valve
Operational Analysis
1
2
3
4
Indigo_Model_Tech.book Page 127 Monday, February 20, 2012 1:17 PM
Summary of Contents for QuietQube Indigo Series
Page 2: ......
Page 22: ...22 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Page 36: ...36 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Page 60: ...60 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Page 110: ...110 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Page 115: ...Part Number STH026 2 12 115 This Page Intentionally Left Blank ...
Page 116: ...116 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Page 157: ...Part Number STH026 2 12 157 This Page Intentionally Left Blank ...
Page 158: ...158 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Page 197: ...Part Number STH026 2 12 197 This Page Intentionally Left Blank ...
Page 209: ...Part Number STH026 2 12 209 This Page Intentionally Left Blank ...
Page 216: ...216 Part Number STH026 2 12 USING PINCH OFF TOOL ...
Page 220: ...220 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Page 233: ...Part Number STH026 2 12 233 I0670C I0870C I1070C I1270C QuietQube Remote Air cooled 1 3 Ph ...
Page 234: ...234 Part Number STH026 2 12 IB0690C IB0890C IB1090C QuietQube Remote Air cooled 1 3 Ph ...
Page 235: ...Part Number STH026 2 12 235 II1400 I1800 I2170 QuietQube Remote Air cooled 1 3 Ph ...
Page 236: ...236 Part Number STH026 2 12 ICVD2095 QuietQube Remote Air cooled 3 Ph ...
Page 243: ...Part Number STH026 2 12 243 This Page Intentionally Left Blank ...
Page 244: ...244 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Page 245: ...Part Number STH026 2 12 245 This Page Intentionally Left Blank ...
Page 246: ...246 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Page 247: ......