184
Part Number STH026 2/12
LOW PRESSURE CUTOUT (LPCO) CONTROL
FUNCTION
Signals the control board to energize and de-energize
the ice machine when suction pressure rises above or
falls below setpoint.
The LPCO control is closed at pressures above
setpoint and opens at pressures below setpoint.
CHECK PROCEDURE
1. Connect manifold gauges at suction and
discharge access valves and verify refrigerant
pressure exceeds LPCO cut-in.
2. Navigate to LPCO input on display
•
Press the Menu button.
•
Scroll down to Service and press right arrow.
•
Scroll down to Diagnostics and press right arrow
•
Scroll down to Inputs and press right arrow to
display LPCO reading
3. LPCO display indicates
A. Open = Replace Switch
B. Closed = Switch OK
Specifications
Cut-Out
Cut-In
12 psig ±3
35 psig ±3
Indigo_Model_Tech.book Page 184 Monday, February 20, 2012 1:17 PM
Summary of Contents for QuietQube Indigo Series
Page 2: ......
Page 22: ...22 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Page 36: ...36 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Page 60: ...60 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Page 110: ...110 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Page 115: ...Part Number STH026 2 12 115 This Page Intentionally Left Blank ...
Page 116: ...116 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Page 157: ...Part Number STH026 2 12 157 This Page Intentionally Left Blank ...
Page 158: ...158 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Page 197: ...Part Number STH026 2 12 197 This Page Intentionally Left Blank ...
Page 209: ...Part Number STH026 2 12 209 This Page Intentionally Left Blank ...
Page 216: ...216 Part Number STH026 2 12 USING PINCH OFF TOOL ...
Page 220: ...220 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Page 233: ...Part Number STH026 2 12 233 I0670C I0870C I1070C I1270C QuietQube Remote Air cooled 1 3 Ph ...
Page 234: ...234 Part Number STH026 2 12 IB0690C IB0890C IB1090C QuietQube Remote Air cooled 1 3 Ph ...
Page 235: ...Part Number STH026 2 12 235 II1400 I1800 I2170 QuietQube Remote Air cooled 1 3 Ph ...
Page 236: ...236 Part Number STH026 2 12 ICVD2095 QuietQube Remote Air cooled 3 Ph ...
Page 243: ...Part Number STH026 2 12 243 This Page Intentionally Left Blank ...
Page 244: ...244 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Page 245: ...Part Number STH026 2 12 245 This Page Intentionally Left Blank ...
Page 246: ...246 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Page 247: ......