Part Number STH026 2/12
173
WATER LEVEL CONTROL CIRCUITRY
FUNCTION
The water level probe controls the water level by
sensing whether water is or is not contacting the water
level probe. The water level probe has three sensing
probes. Two probes are equal in length and are used
to measures conductivity for diagnostics, ice clarity
and water miser options. Factory default settings
measure resistance from both long probes to the short
probe.
SPECIFICATIONS
Freeze Cycle Water Level Setting
During the Freeze cycle, the water level probe is set to
maintain the proper water level above the water pump
housing. The water level is not adjustable. If the water
level is incorrect, check the water level probe position.
Reposition or replace the probe as necessary.
Water Inlet Valve Safety Shut-Off
In the event of a water level probe failure, this feature
limits the water inlet valve to a six-minute on time (8
minutes for dual evaporator models). Regardless of
the water level probe input, the control board
automatically shuts off the water inlet valve when the
time limit is exceeded.
Freeze Cycle Operation
During the Freeze cycle, the water inlet valve
energizes and de-energizes in conjunction with the
water level probe located in the water trough.
During the first 45 seconds of the Freeze cycle:
•
The water inlet valve is
ON
when there is no water
in contact with the water level probes.
•
The water inlet valve turns
OFF
after water
contacts the water level probes for 3 continuous
seconds.
•
The water inlet valve will cycle ON and OFF once
in pre-chill and up to 2 times in the freeze cycle.
After 45 seconds into the Freeze cycle:
The water inlet valve will cycle ON, and then OFF one
more time to refill the water trough. The water inlet
valve is now OFF for the duration of the freeze cycle.
Indigo_Model_Tech.book Page 173 Monday, February 20, 2012 1:17 PM
Summary of Contents for QuietQube Indigo Series
Page 2: ......
Page 22: ...22 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Page 36: ...36 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Page 60: ...60 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Page 110: ...110 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Page 115: ...Part Number STH026 2 12 115 This Page Intentionally Left Blank ...
Page 116: ...116 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Page 157: ...Part Number STH026 2 12 157 This Page Intentionally Left Blank ...
Page 158: ...158 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Page 197: ...Part Number STH026 2 12 197 This Page Intentionally Left Blank ...
Page 209: ...Part Number STH026 2 12 209 This Page Intentionally Left Blank ...
Page 216: ...216 Part Number STH026 2 12 USING PINCH OFF TOOL ...
Page 220: ...220 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Page 233: ...Part Number STH026 2 12 233 I0670C I0870C I1070C I1270C QuietQube Remote Air cooled 1 3 Ph ...
Page 234: ...234 Part Number STH026 2 12 IB0690C IB0890C IB1090C QuietQube Remote Air cooled 1 3 Ph ...
Page 235: ...Part Number STH026 2 12 235 II1400 I1800 I2170 QuietQube Remote Air cooled 1 3 Ph ...
Page 236: ...236 Part Number STH026 2 12 ICVD2095 QuietQube Remote Air cooled 3 Ph ...
Page 243: ...Part Number STH026 2 12 243 This Page Intentionally Left Blank ...
Page 244: ...244 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Page 245: ...Part Number STH026 2 12 245 This Page Intentionally Left Blank ...
Page 246: ...246 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Page 247: ......