CR Series Woodburning Fireplaces

20001316

Cut and Frame Roof Hole

Size of roof hole varies with the type of chimney 
termination installed.  Refer to installation instructions 
provided with the chimney termination to find correct 
size of roof hole.
There must be an air space (1

¹⁄₂

" (38mm) with SK8 ) 

between outermost portion of chimney sections and 
any adjacent combustible surfaces. (Fig. 17) (Com-
bustible surfaces include burnable materials such as:  
ceiling members, joists, flooring, combustible insula-
tion and roof structures.)

WARNING:  Do not pack required air spaces with 
insulation or other materials.

Mark an outline of the roof hole around the center of 
the point nail.  

NOTE:

 Hole dimensions given in the 

chimney top installation instructions are 

horizontal 

dimensions; therefore, the hole size must be marked 
on the roof accordingly.
Cover the opening of the installed chimney so debris 
cannot get into the system.
Cut and frame the hole.  It is good practice to use 
framing lumber that is the same size as the rafters.  
Install the frame securely because the chimney top 
and flashing anchored to the frame must be able to 
withstand heavy winds.

Install Remainder of Chimney Sections

Since you have already preplanned the height of your 
termination according to the 

Ten Foot Rule

, continue 

to install pipe to the predetermined height.

Check the chimney top installation instructions for 
details on how high above the roof top the chimney 
sections (all pipes) should extend.

Installing Top Housing or Termination

Follow the installation instructions provided with the 
CFM Corporation chimney termination you have se-
lected.

Installing Chimney In a Chase

Refer to Page 4, Figure 2 for an illustration of a typical 
chase installation.

CAUTION:

  Treatment of firestop spacers and 

construction of chase may vary with type of build-
ing.  These instructions are not a substitute for local 
building codes.  You 

must

 check your local building 

codes to determine specific requirements for your 
city or state. 

NOTE:

  Other building materials may 

be required in addition to CFM Corporation Firestop 
Spacers.

Finishing

CAUTION:  

All joints between the finished wall and 

the fireplace surround (top/sides) must be sealed with 

noncombustible material to prevent cold air leakage 

into the room. Only noncombustible material may be 

applied to the facing of the fireplace surround.  (Black 

painted area) (Fig. 17)

Side View

FP559CR

Air Spaces

CR Series

3/3/99   djt

Firestop

⁷⁄₁₆

” Air Space 

to Sides

Wall 

Shield

³⁄₄

” Air 

Space to 

Back

0” Clearance 

to Floor

Hearth Extension

Only Noncombus-

tible Material may be 

Applied as Facing to 

the Black Fireplace 

Surround

Combustible Framing Material 

MUST 

NOT

 Penetrate AIR SPACE (Shaded 

Areas)

1

¹⁄₂

” Air Space 

to Combustible 

Materials

Standoff

⁷⁄₁₆

” Air Space 

to Sides

Front View

Air Space Clearances

Fig. 17

 Minimum clearances to combustibles.

FP559CR

Summary of Contents for CR36R

Page 1: ...R36R CR36L CR Series Corner Woodburning Fireplace DO NOT DISCARD THIS MANUAL Retain for future use For use in U S Canada Underwriter s Laboratories Report No MH6018 20001316 4 07 Rev 14 Homeowner s In...

Page 2: ...ed or approved by CFM Corpo ration in combination or assembly with a CFM Corporation replace system notwithstanding any independent testing laboratory or other third party approval of such component p...

Page 3: ...m 21 545mm 172mm 36 914mm 40 1019mm 1054mm Gas Line Access 9 241mm 8 203mm 7 178mm 14 362mm 4 Dia Outside Air Collar Rough Opening Height CR36R L Series Woodburning Fireplace Fig 1 CR36R L Series spec...

Page 4: ...n Grate Firebox Outside Air Control Outside Air Cover Plate Gas Access See Figure 20 on page 15 for clearance information Outer Dome Ceiling Level Firestop Batt Insulation cut out around restop Fig 2...

Page 5: ...himney exit at top CR36L R Series Maximum 90 0 Minimum Without elbows 14 0 With 2 elbows 15 0 With 4 elbows 21 0 B Do not use more than four elbows per chimney Attach the straps of the top elbows to a...

Page 6: ...the surface of the roof a distance of 10 3 m from the chimney in a horizontal plane The top of the chimney must be at least 2 610 mm above the reference point but never less than 3 914 mm in height a...

Page 7: ...ossible Insulate base of replace with a non combus tible insulation rated for a minimum of 300 F Insulating is very important for outside wall installations over a concrete slab If replace is installe...

Page 8: ...and indicate dimension X to locate the side wall framing Fig 8 Be sure to observe clearance requirements for side and parallel combustible walls as noted in Figure 20 Page 15 FP555CR Insulation 2 26 9...

Page 9: ...rip must be fabricated and used to protect combustible surfaces in front of the replace This Z shaped safety strip is not provided but must be fabricated of metal with each horizontal leg at least 1 3...

Page 10: ...alling the Firestop Spacer in the Ceiling Hole A restop spacer is used to keep pipe spaced properly and required for safety Nail the restop spacer at each corner to the framing members of the ceiling...

Page 11: ...insulation is planned to be used in the attic Install the attic insulation shield with the anges on its base extending down into the framing hole Nail each corner of attic insulation shield to the fra...

Page 12: ...predetermined height Check the chimney top installation instructions for details on how high above the roof top the chimney sections all pipes should extend Installing Top Housing or Termination Foll...

Page 13: ...59mm Min 12 305mm Max 12 305mm Max 7 16 1 1 Fig 18 Fireplace surround ush with nished wall FE101a Combustible Mantel and Trim Mantel Clearance No Noncombustible Facing Material Mantel Clearance with N...

Page 14: ...lle CERAFORM 126 K 27 1 2 thick re quired 2 CFM Corporation Building Products EH2416 K 458 1 thick required Hearth Installation A hearth extension is required to protect a combustible oor in front of...

Page 15: ...bustible deco rative covering OR 018 Min Sheet Metal Combustible Floor Minimum Insulation Value R Fireplace Hearth FS108 Sealing Sides 6 22 99 djt Safety Strips must be Overlapped Min Seal Crack Betwe...

Page 16: ...seal between the pipe and the tube NOTE The gas pipe should not come in contact with any wood structures until it has reached a point at least one 1 inch away from the replace side NOTE Local codes m...

Page 17: ...42 20001183 5a Screen Rod Finished 90 7554156 7554155 5b Screen Rod Finished Straight 7554181 7554181 6 Screen Pulls two per replace 5584139 5584139 7a Firebrick Side 20000793 20000794 7b Firebrick Ba...

Page 18: ...he system If you use an unapproved component or make any modi cations you may possibly cause a re hazard and will void the CFM Corporation warranty In addition such action may void the coverage provid...

Page 19: ...alvanized steel unit Roof ashing is included Appropri ate adapter is required See Sections 2 and 3 Required to extend Traditional Top Housings on steeply pitched roofs Used to terminate chimney at the...

Page 20: ...n the roof Flashing not included For use with CFM Corporation Type SK8 Chimney Systems Used to terminate chimney at the top of a chase Adapter kit included Flashing not included 8 6 12 8 ue 0 to 6 12...

Page 21: ...25r Adapter kit CTSK42 3 5 99 djt Chase Top Adapter Kit Hearth Patching Kit 325p r P325p Chase top housings SKDSBL PKDSBL 4 28 99 djt Accessories for Canada Accessory Description Model No Attic Insula...

Page 22: ...22 CR Series Woodburning Fireplaces 20001316...

Page 23: ...installed in the continental United States the state of Alaska and Canada only if and so long as the Fireplace is installed or serviced by a quali ed installer preferably NFI or WETT Canada certi ed...

Page 24: ...410 Admiral Blvd Mississauga Ontario Canada L5T 2N6 800 668 5323 www cfmcorp com CFM Corporation...

Reviews: