background image

11

CR Series Woodburning Fireplaces

20001316

Hole sizes listed in Figure 10 for angled firestop spac-
ers provide minimum required air space to chimney 
pipe for ceiling thickness up to 8” (203mm).  When 
combined thickness of ceiling material, ceiling joists 
and flooring material exceeds 8” (203mm), adjustments 
must be made in framing to assure that minimum air 
spaces to chimney are maintained. 

Proper Firestop Spacer Installation

Page 10, Figure 15 shows different installation proce-
dures for  both an area that 

is

 an attic and  an area that 

is not

 an attic.

If the area above the ceiling

 is not 

an attic, position the 

firestop spacer with the flange on the ceiling side and 
the angled portion extending up into the hole.
If the area above the ceiling 

is

 an attic, position the 

firestop spacer with the flange on the top of the framed 
hole and the angled portion extending down into the 
hole.
Firestop spacers are not available for, nor are they 
required on vertical walls.

DO NOT 

put any sealant around the area where the 

outer pipe slides through the firestop spacer.  If you seal 
this area, 

it may cause a fire hazard.

Canadian Requirements for 

Insulation Shield

In Canada, an attic insulation shield is required to 
prevent attic insulation from contacting the chimney 
section. 

NOTE:

 If the attic insulation shield is used, the 

firestop is not required in the attic installation. Framing 
dimensions for the chimney hole should measure 14

¹⁄₂

x 14

¹⁄₂

"  (368 x 368mm) (SK8). An attic shield MUST 

be installed on top of attic joists (above the floor level). 
(Fig. 16) 

NOTE:

 In the U.S., it is a good idea, although not al-

ways required, to install an attic insulation shield where 
blown-in insulation is planned to be used in the attic.
Install the attic insulation shield with the flanges on its 
base extending down into the framing hole. Nail each 
corner of attic insulation shield to the framing members 
of the ceiling hole using 8d nails.  Attic shields are not 
required at the roof.

Continue Installing Pipe to Complete Run

Continue attaching pipe sections to complete system 
to next level always being careful the pipe is firmly 
snapped locked in place before proceeding to next pipe 
section.

Chimney Supports

If chimney supports are required, they are installed 
the same as elbows.  Nail chimney support straps to 
adjacent structural framing, as shown on Page 7, Figure 
6. Bend straps as necessary and make sure they are 
secure so they will support the weight of the chimney. 
A chimney support is 2

¹⁄₂

" (64mm) long when installed. 

Consider this dimension when determining how many 
straight chimney sections are needed.

Note:

  Chimney supports are generally used in long 

runs in a chase installation. 

A chimney support can-

not be mounted directly to the fireplace.

Additional Ceilings

If you encounter additional ceilings, repeat same steps 
required for first ceiling installation. Refer to firestop 
illustration on Page 10, Figure 15. 

Penetrating the Roof

Run pipe to roofline. Since chimney system must be 
vented to the out-of-doors, you 

must 

use an approved 

termination.
If a chase is used, refer to the installation manual pro-
vided with the termination cap.

Locate Chimney Centerpoint On Roof

Use same procedure detailed in locating center point of 
the flue system.
Drive a nail up through roof at the center point.  This will 
determine center point on outside of the roof.

FP263

Fig. 16  

Attic shield installlation (Canadian requirement).

FP263

Install Attic Insul Shield

5/9/96

Attic 

Insulation 

Shield

Ceiling

Nails

(4 Required)

Attic Joist

Base Flanges

Summary of Contents for CR36R

Page 1: ...R36R CR36L CR Series Corner Woodburning Fireplace DO NOT DISCARD THIS MANUAL Retain for future use For use in U S Canada Underwriter s Laboratories Report No MH6018 20001316 4 07 Rev 14 Homeowner s In...

Page 2: ...ed or approved by CFM Corpo ration in combination or assembly with a CFM Corporation replace system notwithstanding any independent testing laboratory or other third party approval of such component p...

Page 3: ...m 21 545mm 172mm 36 914mm 40 1019mm 1054mm Gas Line Access 9 241mm 8 203mm 7 178mm 14 362mm 4 Dia Outside Air Collar Rough Opening Height CR36R L Series Woodburning Fireplace Fig 1 CR36R L Series spec...

Page 4: ...n Grate Firebox Outside Air Control Outside Air Cover Plate Gas Access See Figure 20 on page 15 for clearance information Outer Dome Ceiling Level Firestop Batt Insulation cut out around restop Fig 2...

Page 5: ...himney exit at top CR36L R Series Maximum 90 0 Minimum Without elbows 14 0 With 2 elbows 15 0 With 4 elbows 21 0 B Do not use more than four elbows per chimney Attach the straps of the top elbows to a...

Page 6: ...the surface of the roof a distance of 10 3 m from the chimney in a horizontal plane The top of the chimney must be at least 2 610 mm above the reference point but never less than 3 914 mm in height a...

Page 7: ...ossible Insulate base of replace with a non combus tible insulation rated for a minimum of 300 F Insulating is very important for outside wall installations over a concrete slab If replace is installe...

Page 8: ...and indicate dimension X to locate the side wall framing Fig 8 Be sure to observe clearance requirements for side and parallel combustible walls as noted in Figure 20 Page 15 FP555CR Insulation 2 26 9...

Page 9: ...rip must be fabricated and used to protect combustible surfaces in front of the replace This Z shaped safety strip is not provided but must be fabricated of metal with each horizontal leg at least 1 3...

Page 10: ...alling the Firestop Spacer in the Ceiling Hole A restop spacer is used to keep pipe spaced properly and required for safety Nail the restop spacer at each corner to the framing members of the ceiling...

Page 11: ...insulation is planned to be used in the attic Install the attic insulation shield with the anges on its base extending down into the framing hole Nail each corner of attic insulation shield to the fra...

Page 12: ...predetermined height Check the chimney top installation instructions for details on how high above the roof top the chimney sections all pipes should extend Installing Top Housing or Termination Foll...

Page 13: ...59mm Min 12 305mm Max 12 305mm Max 7 16 1 1 Fig 18 Fireplace surround ush with nished wall FE101a Combustible Mantel and Trim Mantel Clearance No Noncombustible Facing Material Mantel Clearance with N...

Page 14: ...lle CERAFORM 126 K 27 1 2 thick re quired 2 CFM Corporation Building Products EH2416 K 458 1 thick required Hearth Installation A hearth extension is required to protect a combustible oor in front of...

Page 15: ...bustible deco rative covering OR 018 Min Sheet Metal Combustible Floor Minimum Insulation Value R Fireplace Hearth FS108 Sealing Sides 6 22 99 djt Safety Strips must be Overlapped Min Seal Crack Betwe...

Page 16: ...seal between the pipe and the tube NOTE The gas pipe should not come in contact with any wood structures until it has reached a point at least one 1 inch away from the replace side NOTE Local codes m...

Page 17: ...42 20001183 5a Screen Rod Finished 90 7554156 7554155 5b Screen Rod Finished Straight 7554181 7554181 6 Screen Pulls two per replace 5584139 5584139 7a Firebrick Side 20000793 20000794 7b Firebrick Ba...

Page 18: ...he system If you use an unapproved component or make any modi cations you may possibly cause a re hazard and will void the CFM Corporation warranty In addition such action may void the coverage provid...

Page 19: ...alvanized steel unit Roof ashing is included Appropri ate adapter is required See Sections 2 and 3 Required to extend Traditional Top Housings on steeply pitched roofs Used to terminate chimney at the...

Page 20: ...n the roof Flashing not included For use with CFM Corporation Type SK8 Chimney Systems Used to terminate chimney at the top of a chase Adapter kit included Flashing not included 8 6 12 8 ue 0 to 6 12...

Page 21: ...25r Adapter kit CTSK42 3 5 99 djt Chase Top Adapter Kit Hearth Patching Kit 325p r P325p Chase top housings SKDSBL PKDSBL 4 28 99 djt Accessories for Canada Accessory Description Model No Attic Insula...

Page 22: ...22 CR Series Woodburning Fireplaces 20001316...

Page 23: ...installed in the continental United States the state of Alaska and Canada only if and so long as the Fireplace is installed or serviced by a quali ed installer preferably NFI or WETT Canada certi ed...

Page 24: ...410 Admiral Blvd Mississauga Ontario Canada L5T 2N6 800 668 5323 www cfmcorp com CFM Corporation...

Reviews: