background image

7

CR Series Woodburning Fireplaces

20001316

Angled chimney runs require a support every 6’ (1.8 m) 
in addition to the elbow straps. Chimney supports are 
used for this function. (Fig. 6)

Chase Installation

A chase is a vertical box-like structure which encloses 
the fireplace and/or chimney. Chases are typically built 
on the outside of the house with fireplace opening cut 
into the outer wall of a room. (Page 4, Fig. 2)
If you need help in determining fireplace location or how 
the chimney system should be run, contact your Majes-
tic Fireplaces dealer for assistance.

IWF284

MBUF

5/25/96

FP284

Chimney 

Support 

Strap

SKCS8

Fig. 6 

 Chimney support installation.

Insulating Fireplace Enclosure For 

Cold Climates

If you live in a cold climate, it is not required but 

highly recommended

 that you insulate fire-

place enclosure to eliminate cold air penetration 
as much as possible.
Insulate base of fireplace with a non-combus-
tible insulation rated for a minimum of 300°F.  
Insulating is 

very important

 for outside wall 

installations over a concrete slab. If fireplace 
is installed on a platform, insulation should be 
placed on top of the platform 

before 

fireplace is 

set.(Fig. 7)
When a fireplace is installed in a chase or on an 
outside wall, enclosure should be treated like 
any outside wall in a home. Insulation should 
be installed on the inside wall as well as the 
outside wall(s). In a chase, it is also a good idea 
to install a firestop at the first ceiling level above 
the fireplace and enclose the chase with sheet-
ing material. Insulation may then be installed 
above sheeting material to assure the space 
around the fireplace is totally protected. (Fig. 2)  
When installing the chimney, 

DO NOT

 caulk 

between outer pipe and firestop. It is vital that 
some air be allowed to flow through this very 
thin gap.

CAUTION:  WHEN INSTALLING A FIRE-
PLACE IN AN INSULATED ENCLOSURE, BE 
SURE ALL REQUIRED AIR SPACES ARE 
MAINTAINED. (Page 12, Fig. 17)

Installation

Summary of Contents for CR36R

Page 1: ...R36R CR36L CR Series Corner Woodburning Fireplace DO NOT DISCARD THIS MANUAL Retain for future use For use in U S Canada Underwriter s Laboratories Report No MH6018 20001316 4 07 Rev 14 Homeowner s In...

Page 2: ...ed or approved by CFM Corpo ration in combination or assembly with a CFM Corporation replace system notwithstanding any independent testing laboratory or other third party approval of such component p...

Page 3: ...m 21 545mm 172mm 36 914mm 40 1019mm 1054mm Gas Line Access 9 241mm 8 203mm 7 178mm 14 362mm 4 Dia Outside Air Collar Rough Opening Height CR36R L Series Woodburning Fireplace Fig 1 CR36R L Series spec...

Page 4: ...n Grate Firebox Outside Air Control Outside Air Cover Plate Gas Access See Figure 20 on page 15 for clearance information Outer Dome Ceiling Level Firestop Batt Insulation cut out around restop Fig 2...

Page 5: ...himney exit at top CR36L R Series Maximum 90 0 Minimum Without elbows 14 0 With 2 elbows 15 0 With 4 elbows 21 0 B Do not use more than four elbows per chimney Attach the straps of the top elbows to a...

Page 6: ...the surface of the roof a distance of 10 3 m from the chimney in a horizontal plane The top of the chimney must be at least 2 610 mm above the reference point but never less than 3 914 mm in height a...

Page 7: ...ossible Insulate base of replace with a non combus tible insulation rated for a minimum of 300 F Insulating is very important for outside wall installations over a concrete slab If replace is installe...

Page 8: ...and indicate dimension X to locate the side wall framing Fig 8 Be sure to observe clearance requirements for side and parallel combustible walls as noted in Figure 20 Page 15 FP555CR Insulation 2 26 9...

Page 9: ...rip must be fabricated and used to protect combustible surfaces in front of the replace This Z shaped safety strip is not provided but must be fabricated of metal with each horizontal leg at least 1 3...

Page 10: ...alling the Firestop Spacer in the Ceiling Hole A restop spacer is used to keep pipe spaced properly and required for safety Nail the restop spacer at each corner to the framing members of the ceiling...

Page 11: ...insulation is planned to be used in the attic Install the attic insulation shield with the anges on its base extending down into the framing hole Nail each corner of attic insulation shield to the fra...

Page 12: ...predetermined height Check the chimney top installation instructions for details on how high above the roof top the chimney sections all pipes should extend Installing Top Housing or Termination Foll...

Page 13: ...59mm Min 12 305mm Max 12 305mm Max 7 16 1 1 Fig 18 Fireplace surround ush with nished wall FE101a Combustible Mantel and Trim Mantel Clearance No Noncombustible Facing Material Mantel Clearance with N...

Page 14: ...lle CERAFORM 126 K 27 1 2 thick re quired 2 CFM Corporation Building Products EH2416 K 458 1 thick required Hearth Installation A hearth extension is required to protect a combustible oor in front of...

Page 15: ...bustible deco rative covering OR 018 Min Sheet Metal Combustible Floor Minimum Insulation Value R Fireplace Hearth FS108 Sealing Sides 6 22 99 djt Safety Strips must be Overlapped Min Seal Crack Betwe...

Page 16: ...seal between the pipe and the tube NOTE The gas pipe should not come in contact with any wood structures until it has reached a point at least one 1 inch away from the replace side NOTE Local codes m...

Page 17: ...42 20001183 5a Screen Rod Finished 90 7554156 7554155 5b Screen Rod Finished Straight 7554181 7554181 6 Screen Pulls two per replace 5584139 5584139 7a Firebrick Side 20000793 20000794 7b Firebrick Ba...

Page 18: ...he system If you use an unapproved component or make any modi cations you may possibly cause a re hazard and will void the CFM Corporation warranty In addition such action may void the coverage provid...

Page 19: ...alvanized steel unit Roof ashing is included Appropri ate adapter is required See Sections 2 and 3 Required to extend Traditional Top Housings on steeply pitched roofs Used to terminate chimney at the...

Page 20: ...n the roof Flashing not included For use with CFM Corporation Type SK8 Chimney Systems Used to terminate chimney at the top of a chase Adapter kit included Flashing not included 8 6 12 8 ue 0 to 6 12...

Page 21: ...25r Adapter kit CTSK42 3 5 99 djt Chase Top Adapter Kit Hearth Patching Kit 325p r P325p Chase top housings SKDSBL PKDSBL 4 28 99 djt Accessories for Canada Accessory Description Model No Attic Insula...

Page 22: ...22 CR Series Woodburning Fireplaces 20001316...

Page 23: ...installed in the continental United States the state of Alaska and Canada only if and so long as the Fireplace is installed or serviced by a quali ed installer preferably NFI or WETT Canada certi ed...

Page 24: ...410 Admiral Blvd Mississauga Ontario Canada L5T 2N6 800 668 5323 www cfmcorp com CFM Corporation...

Reviews: