Supply / Exhaust air level
Here you set the required ventilation level for
supply air and exhaust air operation.
In supply air operation, the exhaust air fan is
switched off and the exhaust air shutter is
closed.
In exhaust air operation, the supply air fan is
switched off and the supply air shutter
is closed.
No heat recovery occurs in these
operating modes.
Here you enter the following
parameters, one after the other:
● Supply air ventilation level,
setting values: Level 1 - 4
Factory setting: Ventilation level 2
● Exhaust air ventilation level,
setting values: Level 1 - 4
Factory setting: Ventilation level 2
Filter change, filter change interval
Here you define the intervals at which
the air filter is changed (2...9 months).
After this time has elapsed, icon
(change air filter) appears in the
graphical display.
You can see how long it is until the next filter
change is due through the menu item
"Remaining time until filter change".
Reset the timer to "0" after changing the air
filter.
Here you enter the following
parameters, one after the other:
● Change interval
Setting values: 2...9 moths
(factory setting 6 months)
● Remaining time display
● Reset OFF/ON
Language
Here you define the language of the
display text:
● Setting values, German or English
(Factory setting: German).
Time & Date
Here, you set the current date and time,
see also input example in Chapter 6.1:
● Date in DD.MM.YYYY
● Time in HH:MM
Display fade-out time
Here you define the graphical display
fade-out time:
● Setting values
5 to 30 seconds (factory setting,
10 seconds)
If no operations are carried out during this
time, the display switches off and the system
returns to the starting image.
You should set this value to 30
seconds during setup work,
particularly when setting up network
components.
Rotary knob illumination
(identification light)
Operating knob, blue backlit
Appears when the graphical display is
switched off as an identification light.
Operating knob, red backlit, flashing
Appears in the case of a fault.
Here you enter the following
parameters, one after the other:
● Identification light (blue) setting
Setting values: 0...100 %
(Factory setting, 50%)
● Fault display setting (red, flashing)
Setting values: 20...100 %
(Factory setting, 80 %)
6.10 Service menu
You get to the "Service menu" through the
final menu item in the "Settings" menu.
Confirm with
.
Select the required menu item with
.
Press
.
i
i
GB