36
58-610 Model R82 Radar Transmitter
Display
Action
Comment
19
Flow
Custom Table
Custom Table Type
The following table provides an explanation of each of
the System Configuration parameters for open channel
flow applications using the Custom Table.
P1
P2
P3
P4
P5
Concentrate points along curve
P2
P3
P7
P10
Transition
point
P1
Concentrate points as follows:
A. At least two points at beginning (P1 and P2);
B. At least two points at end (P9 and P10);
C. Three points at approximate average flow rate (for
example, P3, P4, P5); and at transition point (P7)
and points on either side (P6, P8).
P5
P4
P6
P8
P9
Average flow rate
Custom Table Values
A maximum of 20 points can be used in building the
Custom Table
. Each pair of values will have a Head
(height) in the units chosen in the
Level Units
screen, and
the associated flow for that Head value. The values must
be monotonic (i.e., each pair of values must be greater
than the previous Head/flow pair). The last pair of values
should have the highest Head value (usually the
Maximum Head
value) and the flow associated with that
Head value.
SPLINE OR LINEAR
The
Custom Table
points can be a
Linear
(straight line
between adjacent points) or
Spline
(can be a curved line
between points) relationship.