39
58-610 Model R82 Radar Transmitter
Display
Action
Comment
38
Trim 20 mA
Fine tune the 20mA point
Attach a mA meter to the output. If the output does not equal
20.00 mA, adjust the value on the display until meter reads
20.00 mA. This is not for setting the 20mA point (refer to #27).
39
Test 4–20 Loop
(xx.xx mA)
Enter a mA Output value
This screen serves two functions:
1.) Calibrate Loop: Enter mA output value to send a constant
current. Present current will be returned upon exiting screen
2.) Check for sufficient loop voltage @20mA:
a.) Drive current value to 4.00mA
b.) Drive current value to >10mA
c.) Press ENT; top line of display will show
- (????) if done incorrectly
- (OK) if sufficient VDC is calculated
- (Low) if insufficient VDC is calculated
d.) Bottom line of display will show calculated loop voltage
at 20mA
40
Hart Poll Addr
(xx)
Select HART Poll Address
number
Select HART Poll Address number. Select a HART Poll Address
(0-15). Enter 0 for a single transmitter installation; enter 1-15 for
multi-drop HART network.
41
New Password
(enter)
Enter new Password
Enter the desired Password value between 0 and 255; O = No
Password. During normal operation an encrypted password is
shown. Consult factory to decrypt this value, if necessary.
42
Configuration
Reset
Enter to Reset Parameters
Reset configuration parameters to factory default values.
43
Language
(select)
Select Language
Select Language that will be displayed on the transmitter
screen. English, Espanol, Deutsch and Francais.
44
Input Local Tag
(enter)
Enter Local Tag
Local Tag can be a maximum of 12 characters.
45
Magnetrol S/N
Transmitter Display
Shows MAGNETROL Serial Number for reference.
46
Model R82 version
Transmitter Display
Base Model Number with Communication type (HT = HART)
Firmware Version and Date.
47
Factory Params
Enter to display Factory
Parameters
Enter to display Factory Parameters. This section displays
twenty-nine screens. The History screens are of particular
importance to the user as they show a listing of chronological,
diagnostic events, most recent first.
2.6.6.3 Radar Transmitter User Menu—Flow and Level (cont.)
Note: Press UP arrow 5 times to reach screen where menu language can be chosen.