33
58-610 Model R82 Radar Transmitter
2.6.6.3 Radar Transmitter User Menu—Flow and Level (cont.)
Note: Press UP arrow 5 times to reach screen where menu language can be chosen.
Display
Action
Comment
15
Blocking Distance
(xxx.x)
Enter the Blocking Distance
Blocking Distance defines an area near the antenna
where reflections can not be measured effectively due
to antenna ringing. It is measured from the Sensor
Reference point. Default of 15" (380 mm) minimum dis-
tance from the process connection to the maximum level.
Extend this value when necessary to block reflections
from objects close to the antenna. Output will be held
at value corresponding to Blocking Distance. Do not
allow liquid into the Blocking Distance as false readings
can result.
16
Level Offset
(xxx.x units)
Enter the Level Offset
Level Offset defines an area at the bottom of the vessel
where reflections can not be measured effectively due to
angled bottoms, heating coils, reflections from flat metal
tank bottoms in low dielectric applications, etc. It is the
distance from the bottom of the tank to the lowest valid
level reading. Level reading will never be lower than
Level Offset value.
17
Flow Setup
(continued on
next page)
Head
Model R82
Blocking Distance
15" (380 mm) min.
Flow
Water Surface
Throat Section
R
a
n
g
e
R
e
fe
re
n
c
e
D
is
ta
n
c
e
Head
Crest
Channel Floor
B
lo
c
k
in
g
D
is
ta
n
c
e
1
5
"
(3
8
0
m
m
)
m
in
im
u
m
R
a
n
g
e
Weir Plate
Water Surface
R
e
fe
re
n
c
e
D
is
ta
n
c
e
Model R82
Enter the Flow Information
The following table provides an explanation of each of
the System Configuration parameters for open channel
flow applications using one of the Flow Elements that are
stored in the firmware. See below and Pgs. 9–11 for
dimensional information on the flumes and weirs.
Flow Units
A selection of
Gallons/Minute
(factory default Flow Unit),
Gallons/Hour
,
Mil Gallons/Day
,
Liters/Second
,
Liters/Minute
,
Liters/Hour
,
Cubic Meter/Hour
,
Cubic Ft/Second
,
Cubic Ft/Minute
, and
Cubic Ft/Hour
are provided. Should some other units of flow be desired,
the Custom Unit feature can be used in the Advanced
Configuration Menu.
Flume (side view)
Weir
(side view)