20
MPT-333
Technical data
3.5
Control unit MGC
Designation
Value
Power supply
24 V DC
Control unit
max. 1 A max. 300 mA +
current consumption of the differ-
ent plug-in modules
Power consumption
max. 24 W: Max. 7.2 W +
Power consumption of the individu-
al plug-in modules
Control unit safety
1 A T
Output terminal 2
Output voltage
24 V DC
Max. output current
300 mA
Digital inputs
Number
8
Input voltage
24 ± 10 % V DC
Input current
< 10 mA per input
Max. cable length
1)
30 m
Digital outputs
Number
4 (open collector)
Input voltage
24 ± 10 % V DC
Input current
100 mA
Max. cable length
1)
30 m
Relay outputs
Number
3 c 3 changeovers ,
isolated
Max. switching voltage
30 V AC / DC
Switching current
10 mA to 1 A
Max. cable length
1)
30 m
Display
Graphics display, 128 x 65 Pixel
Number of slots for plug-in modules
5
1) Specification without optional overvoltage module. For line lengths exceeding 30 m, overvoltage
modules must be installed in front of the terminal clamps.