Section 8 – Servicing (continued)
Telemotive TR12 inteleSmart Receiver Instruction Manual – 03/01/07
56
Table 8-1. Receiver Diagonostic LED Functions (See Figure 8-1, Receiver Layout for LED locations)
LED COLOR
FUNCTION
DS8
Red
Monitors the ON command from the Transmitter.
LED will flash when an ON command is being received from the Transmitter.
While pushing the ON button on the Transmitter this should light.
DS9
Red
Monitors the OFF command from the Transmitter.
LED will flash when an OFF command is being received from the Transmitter Unit.
While pushing the OFF button on the Transmitter this should light.
DS10
Red
Monitors ESTOP condition.
Normally OFF.
LED will flash when an ESTOP command is transmitted and illuminate continuously when the
ESTOP condition is in effect. An ESTOP condition may be created when an ESTOP command is
transmitted or when a microprocessor failure mode is detected.
DS11 Green
Monitors if the unit is programmed for the “
telePendan
t” Mode.
Normally ON when programmed for the “
telePendan
t” Mode.
Must be ON for the telePendant to work properly on the system. Should be OFF for JLTX, SLTX
and older style 10K pendant operation. See Section 7-11.3 for details.
DS12
Red
Monitors the watchdog timer.
Normally OFF.
The LED will illuminate momentarily when power is applied to or removed from the system. If
the LED is continuously flashing or ON, the computer is not working properly. If LED is ON
constantly (no flashing), the +5 VDC is probably too low. This could be caused by shorts on the
board or by a defective voltage regulator. If the LED flashes at a constant rate, the microcomputer
chip or EPROM may be defective.
DS13 Green
Monitors if the unit is programming mode.
Normally OFF. Is ON for the first 10 seconds the power to the receiver is turned on.
Must be ON to use the PDA to download or upload a program. If OFF, recycle the power switch
SW1.
DS14 Green
Monitors if the unit was successful in communicating with the PDA.
ON if the unit was successful in communicating with the PDA.
If during the current power up settings were successfully sent or received with the PDA this light
turns ON and stays ON till the power is recycled.
DS15 Red
Monitors if the unit is programming mode.
Normally OFF. Flashes ON for the first 10 seconds the power to the receiver is turned on.
Must be flashing to use the PDA to download or upload a program. If OFF, recycle the power
switch SW1. DS15 flashes 5 times before the receiver reverts to normal operation
K1-K12 Red Monitors closure of the output relays (K1-K12).
Normally ON for a function when that specific function is enabled.