in
tele
Smart2 Instruction Manual
June 2016
Page 46 of 49
Receiver is powered
on and transmitter is
powered on and
initialized, but there is
no communication
with receiver (the
receiver seven
segment LED is
displaying 7 after
initialization,
communication LED3
not lighting up)
Project ID in the receiver
and transmitter do not
match
Using RCP, check to make sure the
receiver and transmitter have the same
Project ID number.
Receiver is powered
on and transmitter is
powered on and
initialized, but there is
intermittent
communication with
receiver
(communication LED3
not lighting up)
RF Interference
Check to make sure there are no other
transmitters or communication devices in
the area using the same frequency channel.
Transmitter is out of range Move the transmitter closer to the receiver.
Receiver antenna is
missing or connection is
loose
Check to make sure receiver antenna is
attached and connected properly.
Receiver antenna is
incorrectly mounted
Reference Section 3.3 in the in
tele
Smart2
manual regarding proper receiver antenna
mounting
Receiver is powered
on and transmitter is
powered up, initialized
and communicating
with receiver but no
outputs are
functioning (LED1 is
blinking)
Dot on seven segment
LED not flashing
Firmware download via RCP, or return for
service.
Incorrect relay
configuration in receiver
Using RCP, verify the relay connections.
Change as necessary.
Receiver is powered
on and transmitter is
powered up, initialized
and communicating
with receiver but no
outputs are
functioning (the
receiver seven
segment LED is
displaying a 1)
The processor
encountered an error
during initialization
Consult factory.
Receiver is powered
on and transmitter is
powered up, initialized
and communicating
with receiver but no
outputs are
functioning (the
receiver seven
segment LED is
displaying a 2)
The RF module
encountered an error
during initialization
Consult factory.