39
(7)
Axis calculation acquisition command
Offset
Label
Setting value (Hex)
0
INC
Please enter an arbitrary value different from the value previously
sent.
1
CMD
0x0A
2
RSV1
0x00
3
RSV2
0x00
4
DATA1
※
ASCII code
Frame number
Setting value (Hex)
‘
A
’~’
J
’
0x30
~
0x39
‘
K
’~’
P
’
0x41
~
0x46
5
~
15
DATA2
~
DATA11
Dummy
0x00
(8)
Output type setting command
Offset
Label
Setting value (Hex)
0
INC
Please enter an arbitrary value different from the value previously
sent.
1
CMD
0x0B
2
RSV1
0x00
3
RSV2
0x00
4
DATA1
※
ASCII code
Frame number
Setting value (Hex)
‘
A
’~’
J
’
0x30
~
0x39
‘
K
’~’
P
’
0x41
~
0x46
5
DATA2
※
ASCII code
Output type
Setting value (Hex)
‘0’:
Current values
0x30
‘1’:
Maximum values
0x31
‘2’:
Minimum values
0x32
‘3’:
Peak to peak values
0x33
The output data of the MG70-PN are number of pulses collected from
the measuring unit.
In order to convert those into current values, calculation was needed
in the program.
Current values
= number of pulses× sensor resolution
Output from MG80-PN is measurement value.
It is necessary to remove the calculation program when replacing
MG70-PN to MG80-PN.
6
~
15
DATA3
~
DATA11
Dummy
0x00