Sensopress_LCD_Rev_00_Eng.doc Eng
5
2.4
Technical features
Power Supply
TSL00Y0100
230V~ 50 ÷ 60 Hz
TSL00Y0400
230V~ 50 ÷ 60 Hz
TSL00X0100
117 V~ 50 ÷ 60 Hz
TSL00X0400
117 V~ 50 ÷ 60 Hz
Consumption
5,5 VA
Visualisation
LCD 2x16
Operating temperature
0 ÷ +50 °C
Storage Temperature
-10 ÷ +60 °C
Measuring range
-0.020 ÷ 9 m H
2
O
Maximum overpressure
20 m H
2
O
Accuracy of measurement
± 1% FS
Resolution
1 cm H
2
O
Minimum differential obtainable
2 cm H
2
O
Output Relays
TSL00Y0100
n° 1
(10A 250V~)
TSL00Y0400
n° 4
n° 1 (10A 250V~) + n° 3 (2A 250V~)
TSL00X0100
n° 1 (10A 250V~)
TSL00X0400
n° 4 n° 1 (10A 250V~) + n° 3 (2A 250V~)
Housing
NORYL UL94V0
Dimensions
105x90x73 mm
Weight
450 g
Protection degree
IP20
Approval
CE
Sensors for Sensopress LCD
Code
PRS00B1A1M20000
Housing
BRASS
Principle operation
Ceramic Capsule piezoresistive, calibratedand temperature
compensated
Dimension
32x76 mm
Weight
840 g
Cable
PVC (2 fili + compensation tube) [o PU + SCREEN at instance]
Cable length
20 m
Installation
In or outside the water tank
Measuring range
0 ÷ 9 m H
2
O
Maximum overpressure
20 m H
2
O
Temperature
0 ÷ 50 °C
Storage
15÷30 V 20mA max (as from equipment)
Output
4÷20mA Rt=250 Ohm max (as on the device)
Long term stability
± 0,3%f.s./year at 25°C
Thermal Shift of zero
± 0,02%f.s: /°C
Thermal Shift of span
± 0,01%f.s./°C
Note
It can be used in every kind of water with ph between 5 ÷ 9. For the use
with different liquids, please contact the factory.