13
4.3.2
LOW Mode
This mode is necessay for choosing the low threshold of intervention for the chosen channel.
It is possible to enter the
LOW
mode from whatever other mode by choosing the sign
GO to LOW
with the button Menu and by pushing
yes/+
.
The
LOW
mode allows to set-up the minimum point of intervention. On the display it is shown the
chosen channel ready to be modified (in the single channel version it is shown LOW), the current
minimum threshold identified by the user (HIGH: 638 cm in Figure 7) and the minimum level to be set-
up (Low Level: 012 cm in Figure 7). By pushing the
Yes/+, No/-
buttons it is possible to increase or
decrease the wanted minimum threshold; the minimum threshold cannot exceed the maximum one; if
by mistake the minimum threshold overtakes the maximum one, the value of the minimum one will
start again from 000. With the
Menu
button it is possible to memorize the set-up value and to pass to
the changing state request; if no button is pushed, the device after a few minutes goes to the
AUTO
state.
Figure 7
To set-up the low threshold of a channel which is not the selected one it is necessary to go to the
CHANNEL
mode and choose the wanted channel by following the instructions described in paragraph
4.3.1
CHANNEL Mode.
4.3.3
HIGH Mode
This mode is necessary for setting-up the high threshold of intervention for the chosen channel.
It is possible to enter the
HIGH
Mode from whatever Mode by selecting the sign
GO to HIGH
with the
Menu
button and by pushing
Yes/+
.
The HIGH Mode allows to set-up the maximum point of intervention. On the display it is shown the
selected channel ready to be modified ( in the version with a single output it is shown HIGH), the
current minimum threshold (LOW: 099 cm in Figure 8) and the maximum level to set-up (HIGH
Chosen channel
In the single
output version
it is shown
LOW
Current set-up high threshold for
the chosen channel.
Low threshold possible to set-up
with the Yes/+ e No/- button for the
chosen channel